COLUMBIA BOILER COMPANY OF POTTSTOWN SHALL NOT BE HELD LIABLE FOR<br />

DAMAGE TO THE BOILER CAUSED BY INCORRECT VENT CONDITIONS AND/OR<br />

INSUFFICIENT BURNER MAKEUP AIR.<br />

JACKET ASSEMBLY<br />

The jacket for the <strong>MPH</strong> boiler is factory installed and should not have to be removed for installation<br />

of the boiler.<br />

BURNER MOUNTING<br />

If the burner is to be installed on site, first apply a gasketing material between the burner flange<br />

and the burner mounting plate to seal the burner. Use a non-asbestos fiber rope, or a wet insulating<br />

material for a gasket, as shown in Figure 2. Wet insulation is the preferred gasketing<br />

material because it compresses into a flat gasket which conforms to and fills any and all voids.<br />

Secure the burner in the boiler using the four bolts supplied with the burner. See the Burner Section<br />

of this manual for proper electrical wiring, and fuel supply piping.<br />

Note: All factory packaged boilers use a wet insulation material as a gasket.<br />

Figure 1<br />

<strong>MPH</strong> COLUMBIA BOILER COMPANY 6