IMPORTANT<br />
1. Read and familiarize yourself with this installation, operation, and mainte<br />
nance manual before installing, operating, or servicing your boiler.<br />
2. All cover plates, enclosures, and safety devices must be installed at all<br />
times except while performing maintenance and service.<br />
3. Only trained service technicians should do any work on your boiler.<br />
4. All state and local codes take precedence over any recommendations given<br />
in this manual.<br />
5. <strong>Columbia</strong> Boiler performed testing on the <strong>MPH</strong> boiler line using specific<br />
makes and models of burners. Should you choose to supply your own burner,<br />
please contact the burner manufacturer to confirm compatibility with the<br />
<strong>MPH</strong> boiler design.<br />
6. A barometric damper or draft regulator may be required on <strong>MPH</strong> installations.<br />
A draft regulating device is required on all multiple boiler installations<br />
where the boilers utilize common breaching. One regulator is required per<br />
boiler. Regulators can be installed in each individual boiler breach (Location<br />
A) or in the common breach, just upstream of each connection between the<br />
boiler breach and the common breach. (Location B) One regulator (Location<br />
C) is not acceptable.<br />
1<br />
<strong>MPH</strong> COLUMBIA BOILER COMPANY