Monthly Boiler Check & Maintenance List<br />

1. Test all fan interlocks.<br />

2. Check main burner safety shut off valve(s) for operational closure.<br />

3. Oil fired; check fuel pressure interlocks when provided.<br />

4. Gas fired; check high and low fuel pressure switches.<br />

5. Flue or stack dampers; make visual inspection for proper operation.<br />

6. Inspect heating surfaces for cleanness.<br />

Semiannual Boiler Check & Maintenance List<br />

1. Inspect burner components; Refer to burner manufacturers’ instructions.<br />

2. Check the flame failure system components; Refer to the burner section of this manual.<br />

3. Check piping and wiring of all interlocks and shut off valves.<br />

4. Internal boiler plate inspection. Remove hand-hole assemblies; use new gaskets when<br />

replacing covers.<br />

Annual Boiler Check & Maintenance List<br />

1. Check operating Pressure Control or Aquastat® Controller.<br />

2. Check high limit Pressure Control or Aquastat® Controller.<br />

3. Test safety valves.<br />

4. Remove the Low Water Cut Off and clean inside casting.<br />

5. Oil fired - clean/replace oil filters or strainers if equipped<br />

6. Oil fired - replace ignition electrodes if equipped.<br />

7. Gas pilots - conduct pilot turndown test.<br />

8. Gas fired - replace ignition and flame rods.<br />

9. Gas fired - check drip leg/strainer.<br />

10. Oil fired - check for refractory hold in.<br />

11. Check Automatic Change Over Control if equipped.<br />

12. Gas fired - perform valve leakage test.<br />

Gauge Glass - Not required on hot water boilers only.<br />

The water gauge glass must be kept clean. Dirt on, or in, the glass may be mistaken for the<br />

water level. Do not allow steam or water to leak from the water glass, as this may effect the<br />

accuracy of the level indication. Leaking of the gauge glass will also reduce the wall thickness<br />

of the glass to the point where it may explode.<br />

WARNING:<br />

DO NOT OPERATE THE BOILER WITHOUT THE GAUGE GLASS PROTEC-<br />

TOR INSTALLED. NEVER ATTEMPT TO WORK ON THE GAUGE GLASS<br />

WHILE THE BOILER IS UNDER PRESSURE. ALWAYS CLOSE GAUGE<br />

VALVES PRIOR TO TIGHTENING GASKETS ON WATER LEVEL GAUGE<br />

GLASS. SERIOUS INJURY COULD RESULT.<br />

23<br />