Monthly Boiler Check & Maintenance List<br />
1. Test all fan interlocks.<br />
2. Check main burner safety shut off valve(s) for operational closure.<br />
3. Oil fired; check fuel pressure interlocks when provided.<br />
4. Gas fired; check high and low fuel pressure switches.<br />
5. Flue or stack dampers; make visual inspection for proper operation.<br />
6. Inspect heating surfaces for cleanness.<br />
Semiannual Boiler Check & Maintenance List<br />
1. Inspect burner components; Refer to burner manufacturers’ instructions.<br />
2. Check the flame failure system components; Refer to the burner section of this manual.<br />
3. Check piping and wiring of all interlocks and shut off valves.<br />
4. Internal boiler plate inspection. Remove hand-hole assemblies; use new gaskets when<br />
replacing covers.<br />
Annual Boiler Check & Maintenance List<br />
1. Check operating Pressure Control or Aquastat® Controller.<br />
2. Check high limit Pressure Control or Aquastat® Controller.<br />
3. Test safety valves.<br />
4. Remove the Low Water Cut Off and clean inside casting.<br />
5. Oil fired - clean/replace oil filters or strainers if equipped<br />
6. Oil fired - replace ignition electrodes if equipped.<br />
7. Gas pilots - conduct pilot turndown test.<br />
8. Gas fired - replace ignition and flame rods.<br />
9. Gas fired - check drip leg/strainer.<br />
10. Oil fired - check for refractory hold in.<br />
11. Check Automatic Change Over Control if equipped.<br />
12. Gas fired - perform valve leakage test.<br />
Gauge Glass - Not required on hot water boilers only.<br />
The water gauge glass must be kept clean. Dirt on, or in, the glass may be mistaken for the<br />
water level. Do not allow steam or water to leak from the water glass, as this may effect the<br />
accuracy of the level indication. Leaking of the gauge glass will also reduce the wall thickness<br />
of the glass to the point where it may explode.<br />
WARNING:<br />
DO NOT OPERATE THE BOILER WITHOUT THE GAUGE GLASS PROTEC-<br />
TOR INSTALLED. NEVER ATTEMPT TO WORK ON THE GAUGE GLASS<br />
WHILE THE BOILER IS UNDER PRESSURE. ALWAYS CLOSE GAUGE<br />
VALVES PRIOR TO TIGHTENING GASKETS ON WATER LEVEL GAUGE<br />
GLASS. SERIOUS INJURY COULD RESULT.<br />