Trouble Analysis<br />
H. Discharge pressure too high<br />
Problems and symptoms<br />
Too little or too warm condenser air.<br />
Restricted air flow.<br />
Excessive discharge pressure.<br />
Probable cause<br />
Excessively warm air leaving<br />
condenser.<br />
Cuts out on high pressure control.<br />
Air or noncondensible gas in system.<br />
Recommended action<br />
Clean coil, check fan and motor for<br />
proper operation.<br />
Remove air or non condensibles.<br />
J. Discharge pressure too high<br />
Problems and symptoms<br />
Bubbles in sight glass.<br />
Probable cause<br />
Lack of refrigerant.<br />
Recommended action<br />
Repair leak and charge.<br />
K. Discharge pressure too high<br />
Problems and symptoms<br />
Compressors run continuously.<br />
Abnormally cold suction line; liquid<br />
flood-back to compressor.<br />
Probable cause<br />
Excessive load on evaporator<br />
a) Expansion valve opens too far.<br />
b) Expansion valve stuck in open<br />
position.<br />
Recommended action<br />
Check system.<br />
a) Adjust superheat and check bulb<br />
attachment.<br />
b) Repair or replace.<br />
L. Discharge pressure too high<br />
Problems and symptoms<br />
Bubbles in sight glass.<br />
High pressure drop across filter-driver.<br />
No refrigerant flow through expansion<br />
valve.<br />
Loss of capacity.<br />
Superheat too high.<br />
This is by no means a complete<br />
analysis of the scroll refrigeration<br />
system. Instead, its intention is to<br />
Probable cause<br />
Lack of refrigerant.<br />
Clogged filter drier.<br />
Expansion valve power element has<br />
lost charge.<br />
Obstructed expansion valve.<br />
Too much pressure drop in evaporator.<br />
familiarize the operator with the<br />
operation of the scroll unit and provide<br />
the background necessary for him to<br />
Recommended action<br />
Repair leak, add refrigerant.<br />
Replace.<br />
Replace valve power element.<br />
Clean or replace.<br />
Check external equaliser of expansion<br />
valve.<br />
recognize and accurately correct or<br />
report any developing problem.<br />