Trouble Analysis<br />
A. Compressor fails to starts<br />
Problems and symptoms<br />
Full voltage at motor terminal but motor<br />
will not run.<br />
Inoperative motor starter.<br />
Open contacts of safety control of<br />
thermal overload.<br />
Electric circuit test shows no current<br />
on line side of motor starter.<br />
Electric circuit test show current on line<br />
but not on motor side or fuse.<br />
Voltmeter does not read proper voltage.<br />
Motor starter holding coil is not<br />
energized.<br />
Probable cause<br />
Burned-out motor.<br />
Burned-out holding coil or broken<br />
contacts.<br />
Safety control of thermal overload<br />
relays has cut outs.<br />
a) Power failure.<br />
b) Disconnect switch open.<br />
Fuse down. Replace fuse<br />
Low voltage<br />
Open control circuit.<br />
Compresoor will not operate.<br />
Open contact on high pressure switch.<br />
Discharge pressure above cut-in<br />
setting.<br />
Frozen compressor due to locked or<br />
damaged mechanism<br />
Discharge pressure above cut-in<br />
setting of high pressure cut-out switch<br />
B. Compressor stops<br />
Problems and symptoms<br />
High pressure control has cut out.<br />
Thermal overload relay has cut out.<br />
Winding thermostat has cut out.<br />
Probable Cause<br />
See H.<br />
a) voltage too low<br />
b)cooling load or condensing<br />
temperature too high<br />
Refrigerant shortage<br />
29