Emotron FDU 2.0 Variable Speed Drive

Emotron FDU 2.0 Variable Speed Drive Emotron FDU 2.0 Variable Speed Drive

17.02.2015 Views

. Torque [%] [4161] MaxAlarmMar (15%) [4171] MaxPreAlMar (10%) [41B] 100% Default: T NOM or Autoset: T MOMENTARY [4181] MinPreAlMar (10%) [4191] MinAlarmMar (15%) Max Alarm Max PreAlarm Min Alarm Min PreAlarm Ramp-up phase [413] Ramp Alarm=On [411] Alarm Select=Max or Max0Min [4162] MaxAlarmDel (0.1s) [4172] MaxPreAlDel (0.1s) [414] Start Delay (0.2s) Stationary phase Stationary phase Ramp-down phase [413] Ramp Alarm=On or Off [413] Ramp Alarm=On or Off [413] Ramp Alarm=On [411] Alarm Select=Max or Max0Min [411] Alarm Select=Max or Max0Min [411] Alarm Select=Max or Max0Min [4162] MaxAlarmDel (0.1s) t [s] [4172] MaxPreAlDel (0.1s) Must be

7.6 Pump function 7.6.1 Introduction A maximum of 4 pumps can be controlled with the standard FDU variable speed drive. If I/O Board options are installed, a maximum of 7 pumps can be controlled. The I/O Board can also be used as a general extended I/O. The Pump Control function is used to control a number of drives (pumps, fans, etc., with a maximum of 3 additional drives per I/O-board connected) of which one is always driven by the FDU. Other names for this kind of controllers are 'Cascade controller' or 'Hydrophore controller'. Depending on the flow, pressure or temperature, additional pumps can be activated via the appropriate signals by the output relays of the FDU and/or the I/O Board. The system is developed in such a way that one FDU will be the master of the system. Select relay on the control board or on an option board. The relays are set to functions for controlling pumps. In the pictures in this section, the relays are named R:Function, e.g. R:SlavePump1, which means a relay on the control board or on a option board set to function SlavePump1. PM P1 P2 P3 P4 P5 P6 All additional pumps can be activated via an VSD, soft starter, Y/ Δ or D.O.L. switches. Set PRESSURE Feedback PRESSURE FDU R:SlavePump1 MASTER R:SlavePump2 AnIn PID AnIn PM R:SlavePump3 R:SlavePump4 R:SlavePump5 R:SlavePump6 Pressure Fig. 46 Pressure control with pump control 4 3 2 1 P1 P2 P3 P4 P5 P6 Power Flow (50-PC-2_1) Pumps in parallel will operate as a flow controller, See Fig. 45. Pumps in series will operate as a pressure controller see Fig. 46. The basic control principle is shown in Fig. 47. Set FLOW Feedback FLOW FDU R:SlavePump1 MASTER R:SlavePump2 AnIn PID AnIn R:SlavePump3 R:SlavePump4 R:SlavePump5 R:SlavePump6 NOTE: Read this instruction manual carefully before commencing installation, connecting or working with the variable speed drive. FREQUENCY (master pump P) Add pump Pressure Stop pump Power 1 2 3 4 Flow (50-PC-1_1) P=on P1=on P2=on P3=on P4=on P5=on P6=on FLOW / PRESSURE Fig. 45 Flow control with pump control FLOW / PRESSURE TIM E (50-PC-3_1) Fig. 47 Basic Control principle 40 Main Features Emotron AB 01-4428-01r2

7.6 Pump function<br />

7.6.1 Introduction<br />

A maximum of 4 pumps can be controlled with the standard<br />

<strong>FDU</strong> variable speed drive.<br />

If I/O Board options are installed, a maximum of 7 pumps<br />

can be controlled. The I/O Board can also be used as a general<br />

extended I/O.<br />

The Pump Control function is used to control a number of<br />

drives (pumps, fans, etc., with a maximum of 3 additional<br />

drives per I/O-board connected) of which one is always<br />

driven by the <strong>FDU</strong>. Other names for this kind of controllers<br />

are 'Cascade controller' or 'Hydrophore controller'.<br />

Depending on the flow, pressure or temperature, additional<br />

pumps can be activated via the appropriate signals by the<br />

output relays of the <strong>FDU</strong> and/or the I/O Board. The system<br />

is developed in such a way that one <strong>FDU</strong> will be the master<br />

of the system.<br />

Select relay on the control board or on an option board. The<br />

relays are set to functions for controlling pumps. In the pictures<br />

in this section, the relays are named R:Function, e.g.<br />

R:SlavePump1, which means a relay on the control board or<br />

on a option board set to function SlavePump1.<br />

PM<br />

P1 P2 P3 P4 P5 P6<br />

All additional pumps can be activated via an VSD, soft<br />

starter, Y/ Δ or D.O.L. switches.<br />

Set<br />

PRESSURE<br />

Feedback<br />

PRESSURE<br />

<strong>FDU</strong><br />

R:SlavePump1<br />

MASTER<br />

R:SlavePump2<br />

AnIn<br />

PID<br />

AnIn<br />

PM<br />

R:SlavePump3<br />

R:SlavePump4<br />

R:SlavePump5<br />

R:SlavePump6<br />

Pressure<br />

Fig. 46 Pressure control with pump control<br />

4<br />

3<br />

2<br />

1<br />

P1 P2 P3 P4 P5 P6<br />

Power<br />

Flow<br />

(50-PC-2_1)<br />

Pumps in parallel will operate as a flow controller, See Fig.<br />

45.<br />

Pumps in series will operate as a pressure controller see Fig.<br />

46. The basic control principle is shown in Fig. 47.<br />

Set FLOW<br />

Feedback<br />

FLOW<br />

<strong>FDU</strong><br />

R:SlavePump1<br />

MASTER<br />

R:SlavePump2<br />

AnIn<br />

PID<br />

AnIn<br />

R:SlavePump3<br />

R:SlavePump4<br />

R:SlavePump5<br />

R:SlavePump6<br />

NOTE: Read this instruction manual carefully before<br />

commencing installation, connecting or working with<br />

the variable speed drive.<br />

FREQUENCY (master pump P)<br />

Add pump<br />

Pressure<br />

Stop pump<br />

Power<br />

1 2 3 4<br />

Flow<br />

(50-PC-1_1)<br />

P=on<br />

P1=on P2=on P3=on P4=on P5=on P6=on<br />

FLOW /<br />

PRESSURE<br />

Fig. 45 Flow control with pump control<br />

FLOW /<br />

PRESSURE<br />

TIM E<br />

(50-PC-3_1)<br />

Fig. 47 Basic Control principle<br />

40 Main Features <strong>Emotron</strong> AB 01-4428-01r2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!