Emotron FDU 2.0 Variable Speed Drive

Emotron FDU 2.0 Variable Speed Drive Emotron FDU 2.0 Variable Speed Drive

17.02.2015 Views

7.1.6 Preset references The VSD is able to select fixed speeds via the control of digital inputs. This can be used for situations where the required motor speed needs to be adapted to fixed values, according to certain process conditions. Up to 7 preset references can be set for each parameter set, which can be selected via all digital inputs that are set to Preset Ctrl1, Preset Ctrl2 or Preset Ctrl3. The amount digital inputs used that are set to Preset Ctrl determines the number of Preset References available; using 1 input gives 2 speeds, using 2 inputs gives 4 speeds and using 3 inputs gives 8 speeds. Example The use of four fixed speeds, at 50 / 100 / 300 / 800 rpm, requires the following settings: • Set DigIn 5 as first selection input; set [525] to Preset Ctrl1. • Set DigIn 6 as second selection input; set [526] to Preset Ctrl2. • Set menu [341], Min Speed to 50 rpm. • Set menu [362], Preset Ref 1 to 100 rpm. • Set menu [363], Preset Ref 2 to 300 rpm. • Set menu [364], Preset Ref 3 to 800 rpm. With these settings, the VSD switched on and a RUN command given, the speed will be: • 50 rpm, when both DigIn 5 and DigIn 6 are low. • 100 rpm, when DigIn 5 is high and DigIn 6 is low. • 300 rpm, when DigIn 5 is low and DigIn 6 is high. • 800 rpm, when both DigIn 5 and DigIn 6 are high. 7.2 Remote control functions Operation of the Run/Stop/Enable/Reset functions As default, all the run/stop/reset related commands are programmed for remote operation via the inputs on the terminal strip (terminals 1-22) on the control board. With the function Run/Stp Ctrl [215] and Reset Control [216], this can be selected for keyboard or serial communication control. NOTE: The examples in this paragraph do not cover all possibilities. Only the most relevant combinations are given. The starting point is always the default setting (factory) of the VSD. Default settings of the Run/Stop/ Enable/Reset functions The default settings are shown in Fig. 38. In this example the VSD is started and stopped with DigIn 2 and a reset after trip can be given with DigIn 8. Fig. 38 Default setting Run/Reset commands The inputs are default set for level-control. The rotation is determined by the setting of the digital inputs. Enable and Stop functions Both functions can be used separately or simultaneously. The choice of which function is to be used depends on the application and the control mode of the inputs (Level/Edge [21A]). NOTE: In Edge mode, at least one digital input must be programmed to “stop”, because the Run commands are otherwise only able to start the VSD. Enable Input must be active (HI) to allow any Run signal. If the input is made LOW, the output of the VSD is immediately disabled and the motor will coast. ! RunR Reset +24 V CAUTION: If the Enable function is not programmed to a digital input, it is considered to be active internally. Stop If the input is low then the VSD will stop according to the selected stop mode set in menu [33B] Stop Mode. Fig. 39 shows the function of the Enable and the Stop input and the Stop Mode=Decel [33B]. To run the input must be high. NOTE: Stop Mode=Coast [33B] will give the same behaviour as the Enable input. X1 1 2 3 4 5 6 7 8 9 10 11 X 12 13 14 15 16 17 18 19 20 21 22 Emotron AB 01-4428-01r2 Main Features 35

STOP (STOP=DECEL) OUTPUT SPEED ENABLE OUTPUT SPEED (06-F104_NG) (or if Spinstart is selected) Fig. 39 Functionality of the Stop and Enable input t t Stop RunL RunR Enable Reset +24 V Fig. 40 Example of wiring for Run/Stop/Enable/Reset inputs The Enable input must be continuously active in order to accept any run-right or run-left command. If both RunR and RunL inputs are active, then the VSD stops according to the selected Stop Mode. Fig. 41 gives an example of a possible sequence. X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Reset and Autoreset operation If the VSD is in Stop Mode due to a trip condition, the VSD can be remotely reset by a pulse (“low” to “high” transition) on the Reset input, default on DigIn 8. Depending on the selected control method, a restart takes place as follows: Level-control If the Run inputs remain in their position the VSD will start immediately after the Reset command is given. Edge-control After the Reset command is given a new Run command must be applied to start the VSD again. Autoreset is enabled if the Reset input is continuously active. The Autoreset functions are programmed in menu Autoreset [250]. NOTE: If the control commands are programmed for Keyboard control or Com, Autoreset is not possible. Run Inputs Level-controlled. The inputs are set as default for level-control. This means that an input is activated by making the input continuously “High”. This method is commonly used if, for example, PLCs are used to operate the VSD. INPUTS ENABLE STOP RUN R RUN L OUTPUT STATUS Right rotation Left rotation Standstill Fig. 41 Input and output status for level-control (06-F103new_1) Run Inputs Edge-controlled Menu [21A] Start signal Level/Edge must be set to Edge to activate edge control. This means that an input is activated by a “low” to “high” transition or vice versa. ! CAUTION: Level-controlled inputs DO NOT comply with the Machine Directive, if the inputs are directly used to start and stop the machine. NOTE: Edge-controlled inputs comply with the Machine Directive (see chapter EMC and Machine Directive), if the inputs are directly used for starting and stopping the machine. The examples given in this and the following paragraphs follow the input selection shown in Fig. 40. 36 Main Features Emotron AB 01-4428-01r2

STOP<br />

(STOP=DECEL)<br />

OUTPUT<br />

SPEED<br />

ENABLE<br />

OUTPUT<br />

SPEED<br />

(06-F104_NG)<br />

(or if Spinstart is selected)<br />

Fig. 39 Functionality of the Stop and Enable input<br />

t<br />

t<br />

Stop<br />

RunL<br />

RunR<br />

Enable<br />

Reset<br />

+24 V<br />

Fig. 40 Example of wiring for Run/Stop/Enable/Reset inputs<br />

The Enable input must be continuously active in order to<br />

accept any run-right or run-left command. If both RunR<br />

and RunL inputs are active, then the VSD stops according<br />

to the selected Stop Mode. Fig. 41 gives an example of a possible<br />

sequence.<br />

X1<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

21<br />

22<br />

Reset and Autoreset operation<br />

If the VSD is in Stop Mode due to a trip condition, the<br />

VSD can be remotely reset by a pulse (“low” to “high” transition)<br />

on the Reset input, default on DigIn 8. Depending<br />

on the selected control method, a restart takes place as follows:<br />

Level-control<br />

If the Run inputs remain in their position the VSD will start<br />

immediately after the Reset command is given.<br />

Edge-control<br />

After the Reset command is given a new Run command<br />

must be applied to start the VSD again.<br />

Autoreset is enabled if the Reset input is continuously active.<br />

The Autoreset functions are programmed in menu Autoreset<br />

[250].<br />

NOTE: If the control commands are programmed for<br />

Keyboard control or Com, Autoreset is not possible.<br />

Run Inputs Level-controlled.<br />

The inputs are set as default for level-control. This means<br />

that an input is activated by making the input continuously<br />

“High”. This method is commonly used if, for example,<br />

PLCs are used to operate the VSD.<br />

INPUTS<br />

ENABLE<br />

STOP<br />

RUN R<br />

RUN L<br />

OUTPUT<br />

STATUS<br />

Right rotation<br />

Left rotation<br />

Standstill<br />

Fig. 41 Input and output status for level-control<br />

(06-F103new_1)<br />

Run Inputs Edge-controlled<br />

Menu [21A] Start signal Level/Edge must be set to Edge to<br />

activate edge control. This means that an input is activated<br />

by a “low” to “high” transition or vice versa.<br />

!<br />

CAUTION: Level-controlled inputs DO NOT<br />

comply with the Machine Directive, if the inputs<br />

are directly used to start and stop the machine.<br />

NOTE: Edge-controlled inputs comply with the Machine<br />

Directive (see chapter EMC and Machine Directive), if<br />

the inputs are directly used for starting and stopping the<br />

machine.<br />

The examples given in this and the following paragraphs follow<br />

the input selection shown in Fig. 40.<br />

36 Main Features <strong>Emotron</strong> AB 01-4428-01r2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!