3.6 Thermal protection on the<br />

motor<br />

Standard motors are normally fitted with an internal fan.<br />

The cooling capacity of this built-in fan is dependent on the<br />

frequency of the motor. At low frequency, the cooling capacity<br />

will be insufficient for nominal loads. Please contact the<br />

motor supplier for the cooling characteristics of the motor at<br />

lower frequency.<br />

WARNING: Depending on the cooling<br />

characteristics of the motor, the application,<br />

the speed and the load, it may be necessary<br />

to use forced cooling on the motor.<br />

Motor thermistors offer better thermal protection for the<br />

motor. Depending on the type of motor thermistor fitted,<br />

the optional PTC input may be used. The motor thermistor<br />

gives a thermal protection independent of the speed of the<br />

motor, thus of the speed of the motor fan. See the functions,<br />

Motor I 2 t type [231] and Motor I 2 t current [232].<br />

3.7 Motors in parallel<br />

It is possible to have motors in parallel as long as the total<br />

current does not exceed the nominal value of the VSD. The<br />

following has to be taken into account when setting the<br />

motor data:<br />

Menu [221]<br />

Motor Voltage:<br />

Menu [222]<br />

Motor Frequency:<br />

Menu [223]<br />

Motor Power:<br />

Menu [224]<br />

Motor Current:<br />

Menu [225]<br />

Motor <strong>Speed</strong>:<br />

Menu [227]<br />

Motor Cos PHI:<br />

The motors in parallel must have the<br />

same motor voltage.<br />

The motors in parallel must have the<br />

same motor frequency.<br />

Add the motor power values for the<br />

motors in parallel.<br />

Add the current for the motors in parallel.<br />

Set the average speed for the motors in<br />

parallel.<br />

Set the average Cos PHI value for the<br />

motors in parallel.<br />

20 Installation <strong>Emotron</strong> AB 01-4428-01r2