17.02.2015 Views

Emotron MSF 2.0 Fieldbus Option

Emotron MSF 2.0 Fieldbus Option

Emotron MSF 2.0 Fieldbus Option

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

7.8.3 Response<br />

Bit<br />

Output<br />

from <strong>MSF</strong><br />

Setting<br />

Comment<br />

<strong>MSF</strong> Manual<br />

reference<br />

0<br />

1<br />

2<br />

Running/<br />

Stopped<br />

Max prealarm<br />

status<br />

Min prealarm<br />

status<br />

3 Actual<br />

Parameter<br />

Set<br />

4<br />

5<br />

6 Operation<br />

mode<br />

7<br />

8<br />

9 Operation<br />

status<br />

10<br />

11<br />

12<br />

Running = 1,<br />

Stopped = 0<br />

Pre-alarm = 1<br />

no pre-alarm =0<br />

Pre-alarm = 1<br />

no pre-alarm=0<br />

BIT 5 4 3<br />

Par set 1 = 0 0 1<br />

Par set 2 = 0 1 0<br />

Par set 3 = 0 1 1<br />

Par set 4 = 1 0 0<br />

BIT 8 7 6<br />

1 = 0 0 1<br />

2 = 0 1 0<br />

3= 0 1 1<br />

4 = 1 0 0<br />

5 = 1 0 1<br />

6 = 1 1 0<br />

7 = 1 1 1<br />

BIT 12 11 10 9<br />

1 = 0 0 0 1<br />

2 = 0 0 1 0<br />

3= 0 0 1 1<br />

4 = 0 1 0 0<br />

5 = 0 1 0 1<br />

6 = 0 1 1 0<br />

7 = 0 1 1 1<br />

8 = 1 0 0 0<br />

9 = 1 0 0 1<br />

10 = 1 0 1 0<br />

11 = 1 0 1 1<br />

12 = 1 1 0000<br />

1 = Voltage control<br />

2 = Torque control<br />

3 = Current limit control<br />

4 = Voltage control with current<br />

limit<br />

5 = Torque control with current<br />

limit<br />

7 = Direct On-line<br />

1 = Stopped<br />

2 = Stopped with alarm condition<br />

3 = Run with alarm condition<br />

4 = Run acceleration<br />

5 = Run full voltage<br />

6 = Run deceleration<br />

7 = Run bypassed<br />

8 = Run power factor control<br />

9 = Brake<br />

10 = Run at slow speed forward<br />

11 = Run at slow speed reverse<br />

12= Standby (Waiting for analogue<br />

start/stop or autoreset)<br />

See <strong>MSF</strong> manual<br />

See <strong>MSF</strong> manual<br />

See <strong>MSF</strong> manual<br />

See <strong>MSF</strong> manual<br />

CG Drives & Automation 01-5927-01r0 <strong>Emotron</strong> <strong>MSF</strong> <strong>2.0</strong> 31