17.02.2015 Views

Emotron MSF 2.0 Fieldbus Option

Emotron MSF 2.0 Fieldbus Option

Emotron MSF 2.0 Fieldbus Option

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5.2.2 Connection<br />

Table 3<br />

Connection<br />

Screw Terminal<br />

Description<br />

1 V-<br />

2 CAN_L<br />

3 Shield<br />

4 CAN_H<br />

5 V+<br />

5.2.3 Address<br />

The first 6 switches (DIP1-6) on the DIP switch selects the address. The address<br />

setting on the DIP switch is binary coded with LSB to the left.<br />

5.2.4 Baudrate<br />

There are three different baudrates for DeviceNet; 125k, 250k and 500kbit/s.<br />

Chose one of them by setting the switches (DIP 7-8) on the DIP switch before<br />

configuring.<br />

Table 4<br />

Baudrate<br />

Baudrate (bit/s) DIP 7-8<br />

125k 00<br />

250k 10<br />

500k 01<br />

Reserved 11<br />

5.2.5 Termination<br />

Termination of the fieldbus requires a terminating resistor at each end of the<br />

fieldbus. These resistors should have a value of 121 . Connect resistor between<br />

screw terminal 2 and 4.<br />

14 DeviceNet CG Drives & Automation 01-5927-01r0

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!