15.02.2015 Views

ETS application description - WindowMaster

ETS application description - WindowMaster

ETS application description - WindowMaster

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Motor controller, WEA11M<br />

KNX<br />

Application program <strong>description</strong><br />

25 July 2011<br />

Description<br />

Range<br />

Some locking actuators include a feature, where a special service position can be activated.<br />

This feature is typically used in tilt and turn windows, where the locking actuation for service<br />

can activate the turn state for the window. In order to ease the disengagement of the<br />

window actuator from the sash, a position of the window actuator in service state can be<br />

selected. This parameter rules this service position for window actuator.<br />

0 - 255 counts. The typical distance of one count is 1mm, but it depends of the type of<br />

window actuator.<br />

Parameter<br />

Description<br />

Actuator “locked” indication<br />

Some locking actuators include position switches for determination of the actual position.<br />

Some window hinges do however not allow the locking actuator to reach the final position<br />

but stops at a mechanical stop. This parameter rules whether this situation must be judged<br />

as a mal function or a normal situation.<br />

Range Use switch: Only activation of the switch indicate locked position.<br />

Use overcurrent or switch: Activation of the switch or the mechanical stop will both be<br />

taken as indication for locked positions.<br />