Types of Fire Rated System<br />

Intended use<br />

When considering fire-rated systems, it is important to identify<br />

the intended use of the system under emergency conditions.<br />

An Operational System is one that must remain capable of<br />

operating under emergency conditions (e.g. smoke extract<br />

systems).<br />

A Non-Operational System is one that is designed for<br />

containment purposes and does not need to be operational<br />

under emergency conditions (e.g. kitchen extract).<br />

Period of Protection<br />

The majority of operational systems are usually rated for a<br />

temperature of 300 o C, although some systems can be rated at<br />

400 o C. Typical timescales for operation at this temperature<br />

would be 2 hours. For an operational system, the rating of the<br />

ductwork should match or exceed the rating of the fan.<br />

Non-operational systems may be required to withstand higher<br />

temperatures and/or longer time periods.<br />

Stability, Integrity and Insulation<br />

The “stability” of a system refers to its ability to retain its position,<br />

shape and form for a given time.<br />

The “Integrity” of a system refers to the fire-stopping properties<br />

(e.g. through structural penetrations).<br />

“Insulation” is applied to a system to minimise the effect of<br />

radiant heat.<br />

Fire Rated <strong>Attenuator</strong> Options<br />

Caice/Flameshield Standard Fire-Rated <strong>Attenuator</strong>s<br />

All Caice/Flameshield standard fire rated attenuators would be<br />

suitable for use in operational smoke extract systems with a<br />

rating up to 300 o C for 2 hours.<br />

Enhanced Fire-ratings<br />

Where attenuators are to be installed in any of the following firerated<br />

systems, please contact us for further details as the<br />

products will require an enhanced construction:<br />

<br />

<br />

<br />

<br />

Kitchen Extract<br />

Stair Pressurisation<br />

Smoke Extract in excess of 300°C / 2hours<br />

Other fire-rated rectangular ventilation duct systems<br />

Circular <strong>Attenuator</strong>s<br />

Circular attenuators are not suitable for use in Flameshield fire<br />

rated ductwork systems.<br />

Compatibility with other fire-rated systems<br />

We are aware that some other manufacturers of specialist firerated<br />

ductwork systems may be reluctant to approve the use of<br />

Caice/Flameshield attenuators in their systems, stating either<br />

aesthetic or technical reasons. However, there is no technical<br />

reason why Caice/Flameshield attenuators cannot be used in<br />

other systems.<br />

As various fire-rated systems may differ in appearance and<br />

construction, it is suggested that approval is sought from the<br />

relevant parties before installing Caice/Flameshield attenuators<br />

in any other fire rated system.<br />

In the event that Caice / Flameshield attenuators are not<br />

approved for use, then Caice can offer attenuator products to<br />

match the constructional requirements of any other fire-rated<br />

system at additional cost.<br />