A-60 <strong>Marine</strong> <strong>Fire</strong> <strong>Damper</strong><br />
Insulation Details<br />
Bulkhead (Vertical)<br />
Deck (Horizontal)<br />
STRUCTURAL STEEL CORE<br />
50<br />
25<br />
40 40<br />
DAMPER<br />
See page 7<br />
300<br />
75<br />
See Below<br />
**<br />
COAMING<br />
MINERAL FIBRE<br />
INSULATION<br />
(110Kg PER<br />
CUBIC METRE)<br />
See ** Below<br />
COAMING<br />
225<br />
See ** Below<br />
See page 7<br />
CONNECTION OF DAMPER<br />
TO COAMING<br />
MINERAL FIBRE INSULATION<br />
(110Kg PER CUBIC METRE)<br />
CONNECTION<br />
OF DAMPER<br />
TO COAMING<br />
50<br />
40 25<br />
DAMPER<br />
40<br />
** Table of Minimum Total Coaming Insulation Length<br />
(Applies to all approval bodies)<br />
Application Insulation Thickness Minimum Total Insulation Length<br />
1. Vertical bulkhead up to 750 x 750 (0.5625msq)<br />
75mm<br />
725mm<br />
2. Vertical bulkhead above 0.5625 msq refer to graph below<br />
3. Horizontal deck up to 750 x 750 (0.5625msq)<br />
40mm<br />
725mm<br />
4. Horizontal deck above 0.5625 msq refer to graph below<br />
5. Horizontal deck (all sizes) 75mm 725mm<br />
The same area/insulation criteria applies for multiple arrangements<br />
Graph showing Minimum Insulation length for <strong>Damper</strong> above 750mm x 750mm Base <strong>Damper</strong><br />
(Applies to all approval bodies with the exception of ABS)<br />
Total Insulation length (mm)<br />
1100<br />
1050<br />
1000<br />
950<br />
900<br />
850<br />
800<br />
750<br />
700<br />
0.5 0.55 0.6 0.65 0.7 0.75<br />
0.8 0.85 0.9 0.95 1<br />
Area (msq)<br />
Coaming Insulation<br />
Example<br />
For a damper size of 910mm x 925mm.<br />
Area = 0.85 msq<br />
Vertical Installation<br />
Insulation Thickness = 75mm (line 2 of table)<br />
Insulation Length = 975mm (refer to graph)<br />
Horizontal Installation<br />
Insulation Thickness = 40mm (line 4 of table)<br />
Insulation Length = 975mm (refer to graph)<br />
Insulation Thickness = 75mm (line 5 of table)<br />
Insulation Length = 725mm (line 5 of table)<br />
Note: for circular, use square base damper area.<br />
4