A-60 <strong>Marine</strong> <strong>Fire</strong> <strong>Damper</strong><br />

Insulation Details<br />

Bulkhead (Vertical)<br />

Deck (Horizontal)<br />

STRUCTURAL STEEL CORE<br />

50<br />

25<br />

40 40<br />

DAMPER<br />

See page 7<br />

300<br />

75<br />

See Below<br />

**<br />

COAMING<br />

MINERAL FIBRE<br />

INSULATION<br />

(110Kg PER<br />

CUBIC METRE)<br />

See ** Below<br />

COAMING<br />

225<br />

See ** Below<br />

See page 7<br />

CONNECTION OF DAMPER<br />

TO COAMING<br />

MINERAL FIBRE INSULATION<br />

(110Kg PER CUBIC METRE)<br />

CONNECTION<br />

OF DAMPER<br />

TO COAMING<br />

50<br />

40 25<br />

DAMPER<br />

40<br />

** Table of Minimum Total Coaming Insulation Length<br />

(Applies to all approval bodies)<br />

Application Insulation Thickness Minimum Total Insulation Length<br />

1. Vertical bulkhead up to 750 x 750 (0.5625msq)<br />

75mm<br />

725mm<br />

2. Vertical bulkhead above 0.5625 msq refer to graph below<br />

3. Horizontal deck up to 750 x 750 (0.5625msq)<br />

40mm<br />

725mm<br />

4. Horizontal deck above 0.5625 msq refer to graph below<br />

5. Horizontal deck (all sizes) 75mm 725mm<br />

The same area/insulation criteria applies for multiple arrangements<br />

Graph showing Minimum Insulation length for <strong>Damper</strong> above 750mm x 750mm Base <strong>Damper</strong><br />

(Applies to all approval bodies with the exception of ABS)<br />

Total Insulation length (mm)<br />

1100<br />

1050<br />

1000<br />

950<br />

900<br />

850<br />

800<br />

750<br />

700<br />

0.5 0.55 0.6 0.65 0.7 0.75<br />

0.8 0.85 0.9 0.95 1<br />

Area (msq)<br />

Coaming Insulation<br />

Example<br />

For a damper size of 910mm x 925mm.<br />

Area = 0.85 msq<br />

Vertical Installation<br />

Insulation Thickness = 75mm (line 2 of table)<br />

Insulation Length = 975mm (refer to graph)<br />

Horizontal Installation<br />

Insulation Thickness = 40mm (line 4 of table)<br />

Insulation Length = 975mm (refer to graph)<br />

Insulation Thickness = 75mm (line 5 of table)<br />

Insulation Length = 725mm (line 5 of table)<br />

Note: for circular, use square base damper area.<br />