<strong>Hot</strong><strong>Shield</strong> <strong>PTC</strong> TM<br />
Application and Wiring<br />
Mode HM5 (24V System) and HM5 2H<br />
Supply On – Damper motors open.<br />
Supply Off – Spring closure.<br />
Cable specification:<br />
Si HF Low <strong>Smoke</strong> and Fume, Halogen<br />
Free, to IEC 754-1. Conforming to<br />
73/23/EEC directive.<br />
Release Time ≈ 22 secs.<br />
Reset Time ≈ 60 secs.<br />
(Connect 24V via a safety isolating<br />
transformer.)<br />
IP54 Rated<br />
AC/DC 24V<br />
50 1 / 60 Hz<br />
12.5 VA<br />
10/2 W<br />
Imax<br />
8.3A @ 5ms<br />
–30...+50 C<br />
CONTINUOUS<br />
AC<br />
250V<br />
6(3)A<br />
M<br />
1<br />
2<br />
1<br />
2<br />
3<br />
4<br />
–<br />
+<br />
SUPPLY<br />
24V AC or DC<br />
VOLT FREE CONTACT<br />
CLOSED WHEN<br />
DAMPER RELEASED<br />
VOLT FREE CONTACT<br />
CLOSED WHEN<br />
DAMPER RESET<br />
Mode HM6 (230V System) and HM6 2H<br />
Supply On – Damper motors open.<br />
Supply Off – Spring closure.<br />
Cable specification:<br />
Si HF Low <strong>Smoke</strong> and Fume, Halogen<br />
Free, to IEC 754-1. Conforming to<br />
73/23/EEC directive.<br />
Release Time ≈ 22 secs.<br />
Reset Time ≈ 60 secs.<br />
(To isolate from main power supply, the system must<br />
incorporate a device which disconnects the phase<br />
conductors, with a least 3mm contact gap.)<br />
IP54 Rated<br />
AC 230V<br />
50 / 60 Hz<br />
14 VA<br />
12/4 W<br />
– 30...+50 C<br />
CONTINUOUS<br />
AC<br />
250V<br />
6(3)A<br />
M<br />
BLUE<br />
BROWN<br />
N<br />
L1<br />
1<br />
2<br />
3<br />
4<br />
SUPPLY<br />
230V AC 50/60 Hz<br />
VOLT FREE CONTACT<br />
CLOSED WHEN<br />
DAMPER RELEASED<br />
VOLT FREE CONTACT<br />
CLOSED WHEN<br />
DAMPER RESET<br />
Multiple Assemblies<br />
LHD<br />
STD<br />
RHD<br />
LHD<br />
Square and rectangular casings are<br />
available in multiple module<br />
arrangements, supplied complete with<br />
blanking strips for site assembly by<br />
others. Additional support as well as<br />
provision for thermal expansion<br />
(4mm/metre) should be allowed for on<br />
multiple assemblies.<br />
STD<br />
RHD<br />
STD<br />
RHD<br />
PLAN VIEW<br />
LHD<br />
LHD<br />
STD<br />
RHD<br />
STD<br />
RHD<br />
PLAN VIEW<br />
Multiple assemblies require installation<br />
approval by the relevant local authority.<br />
STD<br />
RHD<br />
LHD<br />
STD<br />
RHD<br />
Approximate Weights (kg)<br />
Square or Circular 100 150 200 250 300 350 400 450 500 550 600 650 70 750 850 850 900 950 1000<br />
Duct Size (mm)<br />
Series 2501 Square 3.4 3.4 3.4 4.2 4.8 5.6 6.5 7.4 8.6 9.6 10.8 12.4 13.6 14.9 16.2 17.7 19.2 20.8 23.5<br />
Series 2501 Square 6.2 6.2 6.2 7.4 8.7 10.3 11.9 13.2 14.6 16.3 18.5 20.5 22.1 24.0 25.9 28.1 30.3 32.4 34.5<br />
+ Installation Frame<br />
Series 2601 Circular 5.3 5.3 5.3 6.1 7.2 8.4 9.6 11.2 12.6 14.0 15.9 17.5 19.1 20.7 22.5 24.3 26.2 29.3 32.1<br />
Series 2601 Circular 8.5 8.5 8.5 10.0 11.9 13.7 15.4 17.1 19.2 21.8 24.0 26.0 28.2 30.4 32.8 35.3 37.8 40.3 43.1<br />
+ Installation Frame<br />
Control Modes 5 and 6 7.6 Kg (including drive interface)<br />
4 www.actionair.co.uk