Technical Data<br />

LV Power Capacitors - Type HPC<br />

Standards<br />

Overvoltage<br />

Overcurrent<br />

Rated Frequency<br />

Tolerance on Capacitance<br />

Test Voltage (Terminal-Terminal)<br />

Test Voltage (Terminal-Casing)<br />

Peak Inrush Current<br />

Operating Losses<br />

Life Expectancy<br />

Degree of Protection<br />

Ambient Temperature Category<br />

Casing Temperature<br />

Cooling<br />

Permissible Relative Humidity<br />

Maximum Allowed Altitude<br />

Installation<br />

Mounting & Earthing<br />

Safety Features<br />

Casing<br />

Dielectric<br />

Terminals<br />

Discharge Resistors / Time<br />

IEC 60831-1 + 2, EN 60831-1 + 2, VDE 0560-46+47<br />

+10% (8h/24h), +15% (30m/24h), +20% (5m x 200<br />

times), +30% ( 1m x 200 times)<br />

1.5 x I n<br />

50/60Hz<br />

-5 / +10% as per standards; ± 5% as per MKS standard<br />

2.15 x U n (AC), 2 sec<br />

≤ 660V, 3000V (AC), 10 sec; > 660V, 6000V (AC), 10 sec<br />

200 x I n<br />

≤ 0.35 W/kVAr, excluding discharge resistor loss<br />

100,000 operating hours<br />

IP20, other options on request<br />

-25/D (maximum 55°C), other categories on request<br />

maximum 65°C measured on top of casing (other values on<br />

request)<br />

Naturally air cooled (or forced cooled)<br />

95%<br />

4000m above sea level<br />

Indoor, Any position<br />

Threaded M12 stud at bottom of casing<br />

Dry Technology<br />

Pressure Sensitive Disconnector for every phase<br />

Self Healing<br />

Extruded Aluminum Type<br />

Polypropylene Film<br />

Protected, Bi-directional, Three phase terminals with heavy<br />

duty clamps suitable for direct termination of 2.5 - 16 mm 2<br />

and 4 - 35mm 2 cables<br />

Resistor Module suitable for External mounting<br />

Standard discharge time range 60 -180 seconds (maximum).<br />

Other discharge times on request<br />

NOTE:<br />

1. The use of Capacitors in Electrical networks with Harmonic presence can result in overloads on the capacitor which are<br />

beyond the permissible levels. In addition there could also be the risk of resonance type effects which can cause amplification<br />

of electrical parameters. Consequently, care must be taken during the process of selecting and using capacitors in such networks<br />

as it may be necessary to install Reactor protected capacitor lines or Harmonic filters.<br />

2. The use of capacitors in Automatic Power Factor Correction cabinets involves the switching of capacitors in parallel. This<br />

can result in high peak inrush currents which are beyond the permissible levels for the capacitors. Care must be taken to ensure<br />

that the correct type of switching devices must be used to ensure that peak inrush currents are within the permissible levels.<br />

6