11.02.2015 Views

Multimax

Multimax

Multimax

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PRODUCT LIST MEASURING DEVICES<br />

MKS<br />

TECHNOLOGY<br />

Measured values Voltage U PH–N (L1-L3) / U PH–PH (L1-L3)<br />

(RMS) Current I PH(L1-L3) / I PH(L1-L3) average (10min. o. assign parameters)<br />

Apparent power S PH (L1-L3) / S total<br />

Active power P PH(L1-L3) / P total<br />

Option:<br />

➾<br />

Light Basic<br />

Frequency f mains - L1<br />

MULTIMESS 96 MULTIMESS PROFIMESS<br />

TYPE Light Basic Eco Light Basic Comfort Basic<br />

Additional<br />

Ripple factor U, Distortion<br />

measured quantities amperage Id / THD<br />

KF-U PH (L1-L3) / I d PH (L1-L3)<br />

–– ● / –– ● / –– ● / ● ● / ● ● / ●<br />

Harmonics Voltage (L1-L3) / Current (L1-L3) –– 3. - 19. Harm. U / –– 3. – 19. Harm. U / –– 3.-19. Harm. U / 3.-19. Harm. I 3.-19. Harm. U / 3.-19. Harm. I 3.-19. Harm. U / 3.-19. Harm. I<br />

Rotating field control Rotating field display in degrees Rotating field display in degrees Rotating field display in degrees –– ––<br />

Neutral current I N / I N-average ● / ● (10min.) ● / ● (10min.) ● / ● (flex. Interval) ● / ● (10min.) ● / ● (10min.)<br />

Power Factor of the fundamental osscilation / Total Power Factor cosϕ L1-3 / λ total cosϕ L1-3 / λ L1-3 only via bus / λ total cosϕ L1-3 / λ total cosϕ L1-3 / λ L1-3 / λ total cosϕ L1-3 / cosϕ average cosϕ L1-3 / cosϕ average<br />

Q 1 = Fundamental oscillation reactive power / Q 1(L1-3) / Q 1total Q 1(L1-3) / Q 1ges Q 1(L1-3) / Q 1total Q 1(L1-3) / Q 1total<br />

Q = Fundamental and harmonic reactive power (Q1 + Q D ) Q (L1-3) / Q total only via bus Q (L1-3) / Q total only via bus<br />

Q1(L1-3) / Q 1total Q 1(L1-3) / Q 1total<br />

Active work / Reactive work –– / ––<br />

–– continuous display at device<br />

––<br />

–– / –– (HT/LT) –– –– –– –– (HT/LT) –– –– –– –– (HT/LT)<br />

Continuous display at device –– read out only via bus! continuous display at device flex. daily work display at device flex. daily work display at device<br />

Displays Type of display LED LED LED LED LED<br />

Measuring accuracy U, I / P, Q, S / cosϕ, λ 1% / 2% / 2% 1% / 2% / 2% 0,5% / 1% / 1% 0,5% / 1% / 1% 0,5% / 1% / 1%<br />

Update speed ≈ 500 ms ≈ 500 ms ≈ 330 ms ≈ 360 ms ≈ 360 ms<br />

Energy consumption<br />

Consumption & Re-generation Consumption & Re-generation<br />

Memory Load profile memory P tot /Q tot (accum.) –– –– –– –– –– P cum / –– –– P cum /<br />

–– P kum / –– Q kum –– –– Qcum –– –– Qcum<br />

Memory capacity of load profiles at 15 minute measuring period –– –– –– Toroidal-core memory for 40 days Toroidal-core memory for 35 days Toroidal-core memory for 35 days<br />

Daily active and reactive work –– –– –– 1 year for energy consumption; 1 year for energy consumption 1 year for energy consumption<br />

read out via bus and re-generation and re-generation<br />

for all displayed Measuring values For all displayed measuring values<br />

Extreme value memory (Min./Max.); slave pointer function For all displayed measuring values + For all displayed measuring values; For all displayed measuring values + max. active power- and reactive + max. active- and reactive power + max. active and reactive power<br />

max. active power average P 15max ; none volatile volatile! power-periods average value P MPmax and Q MPmax with Date & time periods-average value P MPmax and periods-average P MPmax and<br />

(MP=Measuring period) Q MPmax with Date & time Q MPmax with Date & time<br />

(MP=Measuring period)<br />

(MP=Measuring period)<br />

4096 Events with date, time &<br />

duration e.g.: exceeding or falling<br />

Event memory –– –– –– short of set limit; power failures and<br />

Voltage drops ≥20ms at 100%<br />

Measuring voltage drop<br />

200 limit violations<br />

100 power failures 200 limit violations mains failure<br />

100 measuring voltage drops recognition (Bit signal)<br />

with Date, time & duration<br />

Inputs Voltage path U L1-L2 ; U L2-L3 ; U L3-L1 3 x 5V...100V...120V AC & 3 x 5V...100V...120V AC & 3 x 5V...100V...120V AC & 3 x 20V…500V…600V AC 3 x 20V...500V...600V AC<br />

3 x 20V...500V...600V AC 3 x 20V...500V...600V AC 3 x 20V...500V...600V AC ❍ 3 x 5V…100V…120V AC ❍ 3 x 5V...100V...120V AC<br />

Current path I L1 ; I L2 ; I L3 3 x 0,01A…1A…1,2A AC & 3 x 0,01A...1A...1,2A AC & 3 x 0,01A...1A...1,2A AC & 3 x 0,05A…5A…6A AC 3 x 0,05A...5A...6A AC<br />

3 x 0,05A…5A…6A AC 3 x 0,05A...5A...6A AC 3 x 0,05A...5A...6A AC ❍ 3 x 0,01A…1A…1,2A AC ❍ 3 x 0,01A...1A...1,2A AC<br />

1 input to synchronize with utility<br />

Digital inputs –– –– –– Measuring-period & 1 Tariff input to –– ––<br />

switch over HT/LT<br />

Outputs Relay outputs 250V AC / 2A Relay with wiping function –– 2 Relays to signal limit violations 1 Relay to signal limit violations ❍ 1 Relay to signal limit violations<br />

Analogue outputs 0 (4) – 20mA –– –– –– ❍ 1 Analogue output ❍ 1 Analogue output<br />

❍ 2 Analogue outputs<br />

❍ 2 Analogue outputs<br />

Digital outputs open collector –– –– 1 pulse output; proportional to active or reactive work 1 pulse output; proportional to 1 pulse output; proportional to<br />

active or reactive work<br />

active or reactive work<br />

Interfaces Serial interface RS232 / RS485 –– RS485 –– RS485 RS485<br />

RS232 / RS485;<br />

selectable with Jumper<br />

RS485; PROFIBUS-DP<br />

Supported field bus protocols ––<br />

●<br />

Connection from point to point only<br />

●<br />

–– parameterizing of device with own<br />

❍ MODBUS (available soon) protocol ● MODBUS<br />

●<br />

●<br />

Power Supply Operating voltage; power consumption 85-265V AC/DC; 15VA<br />

230V / 115V ±10%; 50/60Hz;<br />

15VA<br />

● 230V±10%;50/60Hz;15VA ● 230V±10%;50/60Hz;15VA<br />

85-265V AC/DC; 15VA ❍ 85-265V AC/DC ❍ 85-265V AC/DC<br />

❍ 20-75 AC / 20-90V DC<br />

❍ 20-75 AC / 20-90V DC<br />

Mechanical data Casing Panel mounting (H x B x T) 96 x 96 x 92 mm 144 x 144 x 60 mm 144 x 144 x 120 mm 144 x 144 x 120 mm<br />

● Regular equipment ❍ Option –– Not available –– = P positive –– = P negative –– = Q positive –– = Q negative Subject to change!<br />