Alarm and Warning codes<br />

Hard Alarms (not resettable)<br />

Code Message Action<br />

-1 Over-temperature reached<br />

Please see chapter on setting the over-temperature<br />

-2 Low-level alarm release Fill with sufficient thermal fluid<br />

-4<br />

-5<br />

-6<br />

-7<br />

-9<br />

-10<br />

-11<br />

-14<br />

-15<br />

-42<br />

-43<br />

-48<br />

-49<br />

-50<br />

-58<br />

actual value internal has<br />

exceeded the alarm temperature<br />

actual value-internal has<br />

exceeded the alarm temperature<br />

actual value process has<br />

exceeded the alarm temperature<br />

Process actual value has fallen<br />

below alarm temperature<br />

PT100 Internal not connected or<br />

faulty<br />

PT100 Process not connected or<br />

faulty<br />

PT100 Condensation not<br />

connected or faulty<br />

Condensation pressure or<br />

temperature too high<br />

Pump speed not correct. Is<br />

pump running?<br />

PT100 return sensor not<br />

connected or faulty<br />

PT100 Evaporator end not<br />

connected or faulty<br />

Evaporation pressure has fallen<br />

below allowed minimum value.<br />

Evaporation pressure is too high<br />

despite controlling<br />

Superheat is too low for a period<br />

Standby current is too high<br />

-59 Current too high when pump is<br />

running<br />

Check alarm limits<br />

Check alarm limits<br />

Check alarm limits<br />

Check alarm limits<br />

Please contact us or our service partners.<br />

Connect a properly functioning external PT100.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners.<br />

Please contact us or our service partners<br />