Compact menu<br />
Here one can switch to the limited possibilities of the compact menu.<br />
Compressor Automatic<br />
Corresponds to Function F35 in the Funct.-no. menu. This is used to select the<br />
operating mode of the compressor. The default setting is always on.<br />
Automatic:<br />
The compressor control is set to switch on and off as required by the unit.<br />
Benefit: Energy saving<br />
Disadvantage: Longer response times to sudden increase in cooling demand.<br />
Always on:<br />
The compressor is always running, so the refrigeration machine is always immediately<br />
available.<br />
Always off:<br />
The compressor is always off.<br />
Compressor Automatic has to be switched to always on when setting process safety in<br />
the main menu point over-temperature protection / OT Mode (only valid for units with<br />
compressors).<br />
Control parameters<br />
A description on this point can be found in the chapter on Compact menu.<br />
Display functions<br />
Following functions are available:<br />
36<br />
1. The brightness of over-temp. and temperature 7-segment displays can be<br />
adjusted here.<br />
2. Warnings (<strong>manual</strong> confirmation or automatic confirmation)<br />
3. Messages (<strong>manual</strong> confirmation or automatic confirmation)<br />
4. Inactive menu items (display / unmask inactive menu items)<br />
5. Temperature resolution (0.01 °C, 0.1 °C)<br />
6. Brightness TFT backlight<br />
7. Go back<br />
Display modes<br />
A description on this menu point can be find in the chapter Compact menu.<br />
E-Grade packages<br />
Here you can enter your activation key in order to extend the functionality of the<br />
controller.