SYS_CRITICAL_IO 81<br />
SYS_CRITICAL_IO<br />
Accumulates the status of safety-critical I/O modules.<br />
Syntax<br />
MY_SYS_CRITICAL_IO( CI:=b1, RESET:=b2, IOP:=n1, SLOT:=n2, APP:=n3,<br />
RELAY_OK:=b3 ) ;<br />
Input Parameters<br />
Name Data Type Description<br />
CI BOOL Enables SYS_CRITICAL_IO.<br />
RESET BOOL Resets.<br />
IOP DINT The IOP (0–15).<br />
SLOT DINT The slot number (0–56).<br />
APP DINT The application number (1-2).<br />
RELAY_OK BOOL The relay is energized and not stuck.<br />
Output Parameters<br />
Name Data Type Description<br />
CO BOOL True if SYS_CRITICAL_IO executes successfully.<br />
TMR BOOL Three channels are operating without faults on all<br />
critical I/O module.<br />
GE_DUAL BOOL At least two channels are operating without faults<br />
on all critical I/O module.<br />
GE_SINGLE BOOL At least one channel is operating without faults on<br />
all critical I/O module.<br />
NO_VOTER_FLTS BOOL No voter faults detected on critical modules.<br />
ERROR_NUM DINT Error Number:<br />
0 = No error.<br />
–1 = The IOP is invalid.<br />
–2 = The slot is not valid.<br />
–3 = The module is not configured.<br />
–4 = The module is the wrong type.<br />
Description<br />
The SYS_CRITICAL_IO function block accumulates the status of safety-critical I/O modules.<br />
<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems