Sample <strong>Safety</strong>-Shutdown Programs 51<br />

Table 10<br />

Parameter<br />

CO<br />

OPERATING<br />

TMR<br />

DUAL<br />

SINGL<br />

ZERO<br />

TIMER_RUNNING<br />

TIME_LEFT<br />

Output Parameters <strong>for</strong> SYS_SHUTDOWN Function Block in EX01_SHUTDOWN<br />

ALARM_PROGRAMMING_PERMITTED<br />

ALARM_REMOTE_ACCESS<br />

ALARM_RESPONSE_TIME<br />

ALARM_DISABLED_POINTS<br />

ERROR_NUM<br />

Description<br />

Control out<br />

When true, all safety-critical modules are<br />

operating properly<br />

When false, the time in degraded operation<br />

exceeds the specified limits; there<strong>for</strong>e, the<br />

control program should shut down the<br />

process<br />

System is operating in triple modular<br />

redundant mode<br />

At least one safety-critical point is controlled<br />

by two channels<br />

At least one safety-critical point is controlled<br />

by one channel<br />

At least one safety-critical point is not<br />

controlled by any channel<br />

Time left to shutdown is decreasing<br />

Time remaining be<strong>for</strong>e shutdown<br />

True if application changes are permitted<br />

True if remote-host writes are enabled<br />

True if actual scan time is greater than<br />

MAX_SCAN_TIME<br />

True if one or more points are disabled.<br />

Error Number:<br />

0 = No error<br />

1 = Error in maximum time<br />

2 = I/O function block error. IO_ERROR is<br />

non-zero<br />

3 = Function block error. System status or MP<br />

Status<br />

<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems