48 Chapter 4 Application Development<br />

value to greater than or equal to zero. The Scan Time parameter in the TriStation 1131 software<br />

Program Execution List applies only when you per<strong>for</strong>m a Download All.<br />

Scan Overrun<br />

If Scan Surplus becomes negative and a scan overrun<br />

occurs, the relevant status attributes are set as follows:<br />

• MP.SCAN_OVERRUNS is incremented once<br />

<strong>for</strong> each time that a longer scan time is<br />

needed.<br />

1 C1<br />

SCAN_STATUS<br />

SYS_MPX_STATUS<br />

CO<br />

REQUESTED_SCAN_TIME<br />

ACTUAL_SCAN_TIME<br />

SURPLUS_SCAN_TIME<br />

SCAN_OVERRUNS<br />

MP.SURPLUS_SCAN_TIME is set to a negative<br />

001<br />

number to indicate the additional time period used by<br />

a scan overrun.For more in<strong>for</strong>mation, see the<br />

TriStation 1131 Developer’s <strong>Guide</strong> and the TriStation 1131 Libraries Reference.<br />

SCAN_SURPLUS<br />

SCAN_OVERRUNS<br />

<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems