48 Chapter 4 Application Development<br />
value to greater than or equal to zero. The Scan Time parameter in the TriStation 1131 software<br />
Program Execution List applies only when you per<strong>for</strong>m a Download All.<br />
Scan Overrun<br />
If Scan Surplus becomes negative and a scan overrun<br />
occurs, the relevant status attributes are set as follows:<br />
• MP.SCAN_OVERRUNS is incremented once<br />
<strong>for</strong> each time that a longer scan time is<br />
needed.<br />
1 C1<br />
SCAN_STATUS<br />
SYS_MPX_STATUS<br />
CO<br />
REQUESTED_SCAN_TIME<br />
ACTUAL_SCAN_TIME<br />
SURPLUS_SCAN_TIME<br />
SCAN_OVERRUNS<br />
MP.SURPLUS_SCAN_TIME is set to a negative<br />
001<br />
number to indicate the additional time period used by<br />
a scan overrun.For more in<strong>for</strong>mation, see the<br />
TriStation 1131 Developer’s <strong>Guide</strong> and the TriStation 1131 Libraries Reference.<br />
SCAN_SURPLUS<br />
SCAN_OVERRUNS<br />