40 Chapter 3 Fault Management<br />

Input/Output Processing<br />

The I/O processor is protected by an independent watchdog that verifies the timely execution<br />

of the I/O processor firmware and I/O module diagnostics. In addition, the I/O processor<br />

reports its sequence of process execution to the MP. If an I/O processor fails to execute correctly,<br />

the MP and the I/O processors enter the fail-safe state and the I/O bus <strong>for</strong> the faulting channel<br />

is disabled, leaving all outputs under control of the remaining healthy channels.<br />

The integrity of the I/O bus is continuously monitored and verified independently by each<br />

channel of the system. A catastrophic bus fault results in affected I/O module channels<br />

reverting to the fail-safe state in less than 500 milliseconds (0.5 seconds), worst case, or less than<br />

10 milliseconds, typically.<br />

I/O Module Alarms<br />

Loss of communication with an I/O module is reported to the control application and can be<br />

used to increase availability during specific multiple-fault conditions.<br />

Main Processor and TriBus<br />

Each Main Processor (MP) module uses memory data comparison between itself and the other<br />

MPs to ensure that the control application executes correctly on each scan. Each MP transfers its<br />

input data to the other two MPs via the TriBus during each scan. Each MP then votes the input<br />

data and provides voted data to the control application. The results of the control application<br />

(outputs), including all internal variables, are transferred by the TriBus. If a mis-compare is<br />

detected, special algorithms are used to isolate the faulting MP. The faulting MP enters the failsafe<br />

state and is ignored by the remaining MPs. Background diagnostics test MP memory and<br />

compare control application instructions and internal status.<br />

The integrity of the TriBus is continuously monitored and verified independently by each MP.<br />

All TriBus faults are detected within the scan associated with the TriBus transfer. Fault isolation<br />

hardware and firmware causes the MP with the faulting TriBus to enter the fail-safe state.<br />

An independent watchdog ensures that the control application and diagnostics execute within<br />

0.5 seconds. If an MP fails to execute the scan, the watchdog <strong>for</strong>ces the MP to the fail-safe state.<br />

The I/O processor adds a sequential element to the MP watchdog. If an MP fails to report the<br />

proper sequence of execution, the I/O processor causes the MP to enter the fail-safe state.<br />