38 Chapter 3 Fault Management<br />

Digital Output Module Alarms<br />

Digital output module faults are reported to the control application and can be used to increase<br />

availability during specific multiple-fault conditions. Loss of field power or logic power is<br />

reported to the control application.<br />

The inability of a digital output module to control an output point is reported to the control<br />

application as a Load/Fuse alarm. This condition can result from a loss of field power or a field<br />

short condition. The alarm can be used to modify the control strategy or direct effective<br />

maintenance action.<br />

Pulse Input (PI) Module<br />

The pulse input module points use a combination of comparison and reference diagnostics.<br />

Under system control, each channel is independently compared against the measured value of<br />

all channels. If a mismatch is found, an alarm is set. Each channel’s measured values are also<br />

compared against the channel’s internal references. These diagnostics are executed<br />

independently by each channel, thus assuring nearly 100 percent fault coverage and fail-safe<br />

operation under all single-fault scenarios, and most common multiple-fault scenarios.<br />

Pulse Input Module Alarms<br />

Pulse input module faults are reported to the control application. These alarms can be used to<br />

increase availability during specific multiple-fault conditions. Loss of logic power is reported to<br />

the control application.<br />

Solid-State Relay Output (SRO) Modules<br />

Solid-state relay output module points are not intended <strong>for</strong> safety-critical applications. The<br />

diagnostics used by the solid-state relay output points cannot detect faults in the relay contacts.<br />

Solid-State Relay Output Module Alarms<br />

Solid-state relay output module faults are reported to the control application.<br />

<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems