32 Chapter 3 Fault Management<br />

Overview<br />

The Tri-GP controller has been designed from its inception with self-diagnostics as a primary<br />

feature. Triple-Modular Redundant (TMR) architecture (shown in Figure 9) ensures fault<br />

tolerance and provides error-free, uninterrupted control in the event of hard failures of<br />

components or transient faults from internal or external sources.<br />

Each I/O module houses the circuitry <strong>for</strong> three independent channels. Each channel on the<br />

input modules reads the process data and passes that in<strong>for</strong>mation to its respective main<br />

processor. The three Main Processor (MP) modules communicate with each other using a<br />

proprietary, high-speed bus system called the TriBus.<br />

Extensive diagnostics on each channel, module, and functional circuit quickly detect and report<br />

operational faults by means of indicators or alarms. This fault in<strong>for</strong>mation is available to an<br />

application. It is critical that an application properly manage fault in<strong>for</strong>mation to avoid an<br />

unnecessary shutdown of a process or plant.<br />

This section discusses the methods <strong>for</strong> properly handling faults.<br />

Input Module<br />

Hot Spare<br />

Output Module<br />

Hot Spare<br />

Input<br />

Channel A<br />

Channel A I/O Bus<br />

Output<br />

Channel A<br />

MP A<br />

(SX)<br />

IOP A<br />

(IOX)<br />

Field<br />

Input<br />

Input<br />

Channel B<br />

Channel B IO/ Bus<br />

MP B IOP B<br />

(SX) (IOX)<br />

TriBus & TriTime<br />

Diagnostic Channel<br />

Output<br />

Channel B<br />

Output Voter<br />

Field<br />

Output<br />

Input<br />

Channel C<br />

Channel C I/O Bus<br />

Output<br />

Channel C<br />

MP C<br />

(SX)<br />

IOP C<br />

(IOX)<br />

Figure 9<br />

Typical <strong>Triconex</strong> Controller<br />

<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems