<strong>Guide</strong>lines <strong>for</strong> <strong>Triconex</strong> Controllers 29<br />
End-user<br />
installed<br />
field wiring<br />
Approved external<br />
termination panel<br />
Approved cable<br />
connects<br />
baseplate to ETP<br />
Approved cable connects<br />
baseplate to ETP (<strong>for</strong> outputs)<br />
Approved external<br />
termination panel<br />
End-user<br />
installed<br />
field wiring<br />
Sensors<br />
External<br />
Termination<br />
Panel<br />
<strong>Triconex</strong><br />
Logic<br />
Solver<br />
External<br />
Termination<br />
Panel<br />
Final<br />
Elements<br />
Boundary of<br />
TÜV-Certified<br />
<strong>Triconex</strong> <strong>Safety</strong> Controller<br />
Figure 8<br />
<strong>Safety</strong> Controller Boundary<br />
Use of Unapproved Components<br />
The use of unapproved cables and unapproved ETPs can negatively impact the safety integrity<br />
of the safety function and the compliance with the applicable safety standards. This causes a<br />
liability issue in the event of a plant incident.<br />
The use of such unapproved components can also impact the availability of the safety system<br />
by causing false trips in the plant. This results in unnecessary economic loss <strong>for</strong> the plant.<br />
<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems