Safety Considerations Guide for Triconex General ... - ICEWeb
Safety Considerations Guide for Triconex General ... - ICEWeb
Safety Considerations Guide for Triconex General ... - ICEWeb
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Hazard and Risk Analysis 7<br />
Sample SIL Calculation<br />
As a PES, the Tri-GP controller is designed to minimize its contribution to the SIL, thereby<br />
allowing greater flexibility in the SIS design.<br />
99.9999 0.000001<br />
R<br />
I<br />
S<br />
K<br />
R<br />
E<br />
D<br />
U<br />
C<br />
T<br />
I<br />
O<br />
N<br />
99.999 0.00001<br />
99.99 0.0001<br />
99.90 0.001<br />
99.00 0.01<br />
90.00 0.1<br />
Tri-GP<br />
PES*<br />
SIL 2 SIS<br />
Percent<br />
Availability<br />
PFD<br />
Risk Measures<br />
Figure 3<br />
Comparison of Percent Availability and PFD<br />
* Tri-GP controller module failure rates, PFD avg , Spurious Trip Rate, and Safe Failure Fraction<br />
(SFF) calculation methods have been independently reviewed by TÜV Rheinland. The numbers<br />
presented here (and in the following tables) are typical. Exact numbers should be calculated <strong>for</strong><br />
each specific system configuration. Contact the Invensys Global Customer Support (GCS) center<br />
<strong>for</strong> details on calculation methods and options related to the Tri-GP controller.<br />
<strong>Safety</strong> Integrated System<br />
3 Pressure<br />
Transmitters (2oo3)<br />
Sensors<br />
3 Temperature<br />
Transmitters (2oo3)<br />
TMR Controller<br />
(2oo3)<br />
PES/Logic Solver<br />
2 Block Valves<br />
in Series (1oo2)<br />
Final Elements<br />
Figure 4<br />
Simplified Diagram of Key Elements<br />
<strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong> <strong>for</strong> <strong>Triconex</strong> <strong>General</strong> Purpose v2 Systems