version 05<br />
Controls for natural ventilation<br />
WUC 101<br />
UniControl Control unit<br />
10 b<br />
Application<br />
– for 24VDC window actuators<br />
– can be combined with external temperature sensor,<br />
timer or BMS<br />
– wind/rain sensor connectable<br />
The control unit can be used for operation of 24VDC window<br />
actuators and other electric accessory products (e.g. Venetian<br />
blinds) with a total current consumption of max. 1A.<br />
The control unit is preset so the actuator automatically travels<br />
to the end-stop after one press of the button. If the button is<br />
pressed for more than two seconds the actuator will run for<br />
as long as the button is pressed.<br />
The control unit has two signal inputs (without priority):<br />
– OPEN/CLOSE function for <strong>WindowMaster</strong> sensors<br />
– keypad type WUI 110<br />
Input signal is to be potential free.<br />
Special technical features<br />
– ventilation function in one group up to 1A<br />
– OPEN/CLOSE function via external ventilation keypad<br />
<strong>WindowMaster</strong> A/S Skelstedet 13 2950 Vedbæk Danmark Tel.: +45 4567 0300 Fax: +45 4567 0390<br />
www.<strong>WindowMaster</strong>.com<br />
<strong>WindowMaster</strong> GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel.: +49 (0) 5731-7583-0 Fax: +49 (0) 5731-7583-79<br />
<strong>WindowMaster</strong> Control Systems Ltd. UNIT 21 Port Tunnel Business Park Dublin 17 Ireland Tel: +353 (0) 1894 1444 Fax: +44 (0) 1536 526321<br />
<strong>WindowMaster</strong> AG Industriestrasse 7 4632 Trimbach Schweiz Tel.: +41 (0) 62 289 22 22 Fax: +41 (0) 62 289 22 20<br />
<strong>WindowMaster</strong> Control Systems Ltd. Kettering Parkway Wellingborough Road Kettering Northants NN15 6XR United Kingdom Tel.: +44 (0) 1536 510990 Fax: +44 (0) 1536 526321
WUC 101<br />
UniControl Control unit<br />
Primary voltage 230 VAC ±10%<br />
Starting current at voltage<br />
Secondary voltage<br />
Open circuit voltage<br />
Standby consumption<br />
Ripple at full load<br />
Operating condition<br />
Switch on duration<br />
max. 6A < 10msec<br />
24 VDC, 1A<br />
27V at 253V<br />
3W at 230V<br />
17% (6Vpp)<br />
-5°C - +45C°, for indoor installation, the control unit may not be covered<br />
ED 40% (max 2min. per 5min.)<br />
Material fire retardant polycarbonate in accordance with UL 94-5V<br />
Colour white (NCS 1000).<br />
Size 182 x 85 x 67mm (Wx H x D)<br />
Weight<br />
IP rating<br />
Delivery includes<br />
Note<br />
1.25kg<br />
IP20<br />
control unit with 1.2m cable and standard plug for connection to the mains supply<br />
we reserve the right to make technical changes<br />
Actuator type<br />
Max. number of actuators,<br />
can be connected to the control unit.<br />
Secondary voltage (max. 27V)<br />
Actuator type<br />
Max. number of actuators,<br />
can be connected to the control unit.<br />
Secondary voltage (max. 27V)<br />
WMB 801/802 1 WMX 802-n 1<br />
WMI 101 1 WMX 804-n 1<br />
WML 825 1 WMX 820-n 1<br />
WMU 100 1 WMX 824-n 1<br />
WMU 861-n<br />
Item<br />
Item no.<br />
UniControl control unit WUC 101 WUC 101 0105<br />
UniControl control unit WUC 101 (UK version) WUC 101 0402<br />
Accessories<br />
Item no.<br />
UniControl operating keypad for WUC 101 and WUC 102 WUI 110 0102<br />
Ventilation push-button, flush mounting WSK 100 1161<br />
Ventilation push-button WSK 102<br />
Room thermostat WLA 110<br />
Timer 230 VAC (wall mounting surround WAB 122 to be ordered separately) WLA 120<br />
Wind/rain sensor WLA 330<br />
Rain sensor WLA 331<br />
©<strong>WindowMaster</strong> 2005, 2010 ®<strong>WindowMaster</strong> is a registered trademark used under license by <strong>WindowMaster</strong> Group<br />