Chapter 4 Explanation of Functions<br />

(2) Output of the alarms for instantaneous power failure and undervoltage in the stopped state<br />

Use function "b004" to specify whether to output an alarm when instantaneous power failure or<br />

undervoltage occurs.<br />

The inverter outputs the alarm providing the control power remains in the inverter.<br />

Output of the alarms for instantaneous power failure and undervoltage in the stopped state<br />

Examples 5 to 7 show the alarm output operations with standard settings. Examples 8 to 10 show the<br />

alarm output operations with the settings to supply DC power (P-N) to control power supply terminals R0<br />

and T0.<br />

(Example 5) b004:00<br />

Power supply<br />

While the inverter is stopped<br />

Power supply<br />

While the inverter is operating<br />

Operation command<br />

Operation command<br />

Inverter output<br />

Inverter output<br />

(Example 6) b004:01<br />

Power supply<br />

While the inverter is stopped<br />

Power supply<br />

While the inverter is operating<br />

Operation command<br />

Operation command<br />

Inverter output<br />

Inverter output<br />

(Example 7) b004:02<br />

Power supply<br />

While the inverter is stopped<br />

Power supply<br />

While the inverter is operating<br />

Operation command<br />

Operation command<br />

Inverter output<br />

Inverter output<br />

(Example 8) b004:00<br />

Power supply<br />

Operation command<br />

Inverter output<br />

While the inverter is stopped<br />

While the inverter is operating<br />

Power supply<br />

Operation command<br />

Inverter output<br />

(Example 9) b004:01<br />

Power supply<br />

Operation command<br />

Inverter output<br />

While the inverter is stopped<br />

Undervoltage<br />

While the inverter is operating<br />

Power supply<br />

Operation command<br />

Inverter output<br />

(Example 10) b004:02<br />

Power supply<br />

Operation command<br />

Inverter output<br />

While the inverter is stopped<br />

While the inverter is operating<br />

Power supply<br />

Operation command<br />

Inverter output<br />

Note 1: You can assign the instantaneous power failure alarm signal (IP: 08) and the undervoltage alarm<br />

signal (UV: 09) to any of the intelligent output terminals [11] to [15] (C021 to C025) and the alarm<br />

relay terminal (C026) to output the alarm signals.<br />

Note 2: For the alarm output following the occurrence of power failure of 1 second or longer, see the<br />

explanation of reset (Section 4.2.48).<br />

4 - 35