Chapter 4 Explanation of Functions<br />

4.2.27 Retry or trip after instantaneous power failure<br />

(1) Retry (restart) after instantaneous power failure<br />

You can select tripping or retrying (restarting) the motor<br />

operation as the inverter operation to be performed at the<br />

occurrence of instantaneous power failure or undervoltage.<br />

If you specify a retry operation for the selection of restart mode<br />

(b001), the inverter will retry the motor operation for the number<br />

of times set as "b005" after an instantaneous power failure or<br />

the number of times set as "b009" after overvoltage<br />

respectively, and then trip if all retries fail. (The inverter will not<br />

trip if you specify an unlimited number of retries.)<br />

With function "b004" you can select whether to make the inverter trip when an instantaneous power failure<br />

or undervoltage occur while the inverter is in a stopped state.<br />

When selecting a retry operation, also set the retry conditions listed below according to the system to be<br />

driven by the inverter.<br />

Even during a retry operation, the inverter will trip with error code "E09" (undervoltage) displayed if the<br />

undervoltage status continues for 40 seconds.<br />

Item<br />

Function code<br />

Data or range of<br />

data<br />

Description<br />

00 Tripping<br />

01 Restarting the motor with 0 Hz at retry<br />

Starting the motor with a matching frequency at retry<br />

02<br />

(See example 1.) (*3)<br />

Selection of restart mode<br />

b001<br />

(*4) (*6)<br />

Starting the motor with a matching frequency at retry<br />

03<br />

The inverter trips after decelerating and stopping the<br />

motor. (*1) (*3)<br />

04<br />

Restarting the motor with an input frequency at retry<br />

(See example 1.) (*3)<br />

Restarting the motor when the power failure duration does<br />

Allowable under-voltage<br />

not exceed the specified time (See example 1.)<br />

b002 0.3 to 25.0 (s)<br />

power failure time<br />

Tripping when the power failure duration exceeds the<br />

specified time (See example 2.)<br />

Retry wait time before<br />

motor restart<br />

b003 0.3 to 100. (s) Time to wait until restarting the motor<br />

00 Disabling the inverter from tripping<br />

Instantaneous power<br />

01 Enabling the inverter to trip<br />

failure/under-voltage trip<br />

alarm enable (*2) (*4)<br />

b004<br />

02<br />

Disabling the inverter from tripping when the inverter is<br />

stopped or while the motor is being decelerated or<br />

stopped after the operation command has been turned off<br />

Retrying the motor operation up to 16 times after<br />

Number of restarts on<br />

00<br />

instantaneous power failure<br />

power failure/under-voltage b005<br />

trip events<br />

Retrying the motor operation an unlimited number of times<br />

01<br />

after instantaneous power failure<br />

Restarting the motor with 0 Hz if the frequency becomes<br />

Restart frequency threshold b007 0.00 to 400.0 (Hz) less than the frequency set here during motor free-running<br />

(See examples 3 and 4.)<br />

00 Tripping<br />

01 Restarting the motor with 0 Hz at retry<br />

02 Starting the motor with a matching frequency at retry<br />

Trip/retry selection<br />

b008<br />

03<br />

Starting the motor with a matching frequency at retry<br />

The inverter trips after decelerating and stopping the<br />

motor.<br />

04 Restarting the motor with an input frequency at retry<br />

Retrying the motor operation up to 16 times after<br />

00<br />

Selection of retry count<br />

undervoltage<br />

b009<br />

after undervoltage<br />

Retrying the motor operation an unlimited number of times<br />

01<br />

after undervoltage<br />

Selection of retry count<br />

Number of retries to be made after the occurrence of<br />

after overvoltage or<br />

b010 1 to 3 (times)<br />

overvoltage or overcurrent (*5)<br />

overcurrent<br />

Retry wait time after<br />

overvoltage or overcurrent<br />

b011 0.3 to 100. (s) Time to wait until restarting the motor<br />

Active frequency matching,<br />

restart frequency select<br />

Active frequency matching,<br />

scan start frequency<br />

Active frequency matching,<br />

scan-time constant<br />

b030<br />

b028<br />

b029<br />

00 Frequency set when the inverter output has been shut off<br />

01 Maximum frequency<br />

02 Newly set frequency<br />

"0.20 x rated<br />

current" to "2.00 x Current limit for restarting with active matching frequency<br />

rated current"<br />

0.10 to 30.00 (s)<br />

Duration of frequency lowering when restarting with active<br />

matching frequency<br />

4 - 33<br />

Related code<br />

b001: Selection of restart mode<br />

b002: Allowable under-voltage power failure time<br />

b003: Retry wait time before motor restart<br />

b004: Instantaneous power failure/under-voltage<br />

trip alarm enable<br />

b005: Number of restarts on power<br />

failure/under-voltage trip events<br />

b007: Restart frequency threshold<br />

b008: Selection of retry count after undervoltage<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function