Safety <strong>Instruction</strong>s<br />

Precautions Concerning Compliance with UL and CUL Standards<br />

(Standards to be met: UL508C and CSA C22.2 No. 14-05)<br />

The <strong>SJ700</strong> series inverter is an open-type AC inverter with 3-phase input and output, intended for use in<br />

an enclosure. The inverter supplies both voltage and frequency, both of which are adjustable, to an AC<br />

motor. The inverter can automatically maintain a constant volts/Hz ratio to enhance the motor capability<br />

throughout its entire speed range.<br />

1. Only 75C CU or equivalent wires must be used for wiring.<br />

2. Inverter models with the suffix "L" (200 V class models) are suited to circuits that transmit current not<br />

exceeding 100k rms symmetrical amperes and with voltage of no more than 240 V.<br />

3. Inverter models with the suffix "H" (400 V class models) are suited to circuits that transmit current not<br />

exceeding 100k rms symmetrical amperes and with voltage of no more than 480 V.<br />

4. Suitable for use on a circuit capable of delivering not more than 100 k rms symmetrical amperes, 480 V<br />

maximum”. For models with suffix H.<br />

5. “Install device in pollution degree 2 environment”.<br />

6. “Maximum Surrounding Air Temperature 50°C”<br />

7. “CAUTION- Risk of Electric Shock- Capacitor discharge time is at least 10 min.” “Use 75C CU wire<br />

only”<br />

8. “Solid state motor overload protection is provided in each model”<br />

9. Tightening torque and wire range for field wiring terminals in the table below:<br />

Model No. Required torque (N-m) Wire range (AWG)<br />

<strong>SJ700</strong>-004L 1.8 14(Stranded only)<br />

<strong>SJ700</strong>-007L 1.8 14(Stranded only)<br />

<strong>SJ700</strong>-015L 1.8 14(Stranded only)<br />

<strong>SJ700</strong>-022L 1.8 14(Stranded only)<br />

<strong>SJ700</strong>-037L 1.8 10(Stranded only)<br />

<strong>SJ700</strong>-050L 3.0 8<br />

<strong>SJ700</strong>-055L 4.0 8<br />

<strong>SJ700</strong>-075L 4.0 6<br />

<strong>SJ700</strong>-110L 4.0 6-4<br />

<strong>SJ700</strong>-150L 4.9 2<br />

<strong>SJ700</strong>-185L 4.9 1<br />

<strong>SJ700</strong>-220L 8.8 1 or 1/0<br />

<strong>SJ700</strong>-300L 8.8 2/0 or Parallel of 1/0<br />

<strong>SJ700</strong>-370L 20.0 4/0 (Prepared wire only) or Parallel of 1/0<br />

<strong>SJ700</strong>-450L 20.0 4/0 (Prepared wire only) or Parallel of 1/0<br />

<strong>SJ700</strong>-550L 19.6 350 kcmil<br />

(Prepared wire only) or Parallel of 2/0 (Prepared wire only)<br />