Chapter 4 Explanation of Functions<br />

4.2.20 Frequency upper limit setting<br />

The frequency upper limit setting function allows you to place<br />

upper and lower limits on the inverter output frequency.<br />

This function restricts the input of frequency commands that<br />

specify any frequencies outside the upper and lower limits.<br />

Always set the upper limit before setting the lower limit. Also, be sure to keep the frequency upper limit<br />

(A061/A261) larger than the frequency lower limit (A062/A262).<br />

Be sure that upper limit/lower limit does not exceed Maximum frequency (A004/A204/A304).<br />

Be sure to set output frequency (F001) and multiple speed 1 to 15 (A021 to A035) in between uppelimit<br />

and lower limit.<br />

If 0 Hz is set for the frequency upper and lower limits, they will not operate.<br />

The frequency limit setting function is disabled when the 3rd control system is selected.<br />

Item Function code Range of data Description<br />

0.00 or a frequency more than the<br />

A061/A261 frequency lower limit setting up to the<br />

maximum frequency (Hz)<br />

Frequency upper<br />

limit setting<br />

Frequency lower<br />

limit setting<br />

A062/A262<br />

0.00 or a frequency not less than the<br />

starting frequency up to the frequency<br />

upper limit setting (Hz)<br />

Related code<br />

A061/A261: /Frequency upper limit setting,<br />

1st/2nd motors<br />

A062/A262: Frequency lower limit setting,<br />

1st/2nd motors<br />

Setting of the upper limit of the<br />

output frequency<br />

Setting of the lower limit of the<br />

output frequency<br />

(1) When the O-L or OI-L terminal is used:<br />

Output frequency (Hz)<br />

Maximum frequency<br />

A004/A204<br />

A061<br />

If 0 V or 4 mA is input as the frequency command<br />

when a frequency lower limit has been set for the<br />

frequency lower limit setting (A062), the inverter<br />

will output the set frequency.<br />

A062<br />

0 V<br />

4 mA<br />

(2) When the O2-L terminal is used:<br />

Maximum frequency<br />

A004/A204<br />

A061<br />

10 V<br />

20 mA<br />

Frequency command<br />

Reverse rotation<br />

-10 V<br />

A062<br />

Forward rotation<br />

A062<br />

10 V<br />

A061<br />

Maximum frequency<br />

A004/A204<br />

If the frequency lower limit is used with the frequency command input via the O2-L terminal, the motor<br />

speed with 0 V input will be fixed to the frequency setting of the frequency lower limit (A062) for forward<br />

rotation or the frequency setting of the frequency lower limit (A062) for reverse rotation as shown below.<br />

(a) When operation commands are input via the control circuit terminal block (A002: 01)<br />

Terminal Motor speed with 0 V input via O2 terminal<br />

FW(ON) Frequency setting by A062 for forward rotation<br />

RV(ON) Frequency setting by A062 for reverse rotation<br />

(b) When operation commands are input from the digital operator (A002: 02)<br />

F004 Motor speed with 0 V input via O2 terminal<br />

00 Frequency setting by A062 for forward rotation<br />

01 Frequency setting by A062 for reverse rotation<br />

4 - 24