Chapter 4 Explanation of Functions<br />

(3) Internal DC braking (A051: 01)<br />

You can apply DC braking to the motor even without entering braking signals via the DB terminal when the<br />

inverter starts and stops. To use the internal DC braking function, specify "01" for the DC braking enable<br />

(A051).<br />

Use function "A057" to set the DC braking force for starting, and use function "A058" to specify the DC<br />

braking time for starting, regardless of the braking mode selection (edge or level mode). (See examples<br />

4-a and 4-b.)<br />

Set the braking force for periods other than starting by using the DC braking force setting (A054).<br />

Set the output frequency at which to start DC braking by using the DC braking frequency setting (A052).<br />

When you set the DC braking wait time (A053), the inverter output will be shut off when the output<br />

frequency reaches the setting of "A052" after the operation command (FW signal) is turned off, and the<br />

motor will run freely for the delay time set by "A053". DC braking will be started after the delay (A053).<br />

The internal DC braking operation to be performed when the operation command is switched from the stop<br />

command to the start command varies depending on the braking mode (edge or level mode).<br />

Edge mode: The DC braking time setting (A055) is given priority over operation commands, and the<br />

inverter performs DC braking according to the setting of "A055". When the output frequency<br />

reaches the setting of "A052" the inverter performs DC braking for the time set for "A055".<br />

Even if the stop command is input during DC braking, DC braking continues until the time<br />

set for "A055" elapses. (See examples 5-a and 6-a.)<br />

Level mode: Operation commands are given priority over the DC braking time setting. The inverter<br />

follows operation commands, regardless of the DC braking time setting (A055). If the start<br />

command is input during DC braking, the inverter starts the normal motor operation,<br />

regardless of the DC braking time setting (A055). (See examples 5-b and 6-b.)<br />

(a) Edge mode<br />

(b) Level mode<br />

i) (Example 4-a) when the start command is input: i) (Example 4-b) when the start command is input:<br />

FW<br />

FW<br />

Output<br />

frequency<br />

Output<br />

frequency<br />

A057<br />

A057<br />

A058<br />

A058<br />

ii) (Example 5-a) when the stop command is input:<br />

FW<br />

ii) (Example 5-b) when the stop command is input:<br />

FW<br />

Output<br />

frequency<br />

Free running<br />

Output<br />

frequency<br />

Free running<br />

A052<br />

A053<br />

A055<br />

A052<br />

A053<br />

A055<br />

ii) (Example 6-a) when the stop command is input:<br />

FW<br />

ii) (Example 6-b) when the stop command is input:<br />

FW<br />

Output<br />

frequency<br />

Output<br />

frequency<br />

A052<br />

A055<br />

A052<br />

A055<br />

4 - 22