Chapter 4 Explanation of Functions<br />

(2) External DC braking<br />

Assign function "07" (DB) to terminal function (C001 to C008).<br />

Turn the DB terminal on and off to control the direct braking, regardless of the setting of DC braking enable<br />

(A051).<br />

Adjust the braking force by adjusting the DC braking force setting (A054).<br />

When you set the DC braking wait time (A053), the inverter output will be shut off for the set period of delay,<br />

and the motor will run freely during the period. DC braking will be restarted after the delay.<br />

When setting the DC braking time with function "A055" or for the DC braking operation via the DB terminal,<br />

determine the length of time in consideration of the heat generation on the motor.<br />

Select the braking mode by the DC braking/edge or level detection for [DB] input (A056), and then make<br />

any other necessary settings suitable for your system.<br />

(a) Edge mode (A056: 00) (b) Level mode (A056: 01)<br />

(Example 1-a)<br />

FW<br />

(Example 1-b)<br />

FW<br />

DB<br />

DB<br />

Output<br />

frequency<br />

Output<br />

frequency<br />

A055<br />

(Example 2-a)<br />

(Example 2-b)<br />

FW<br />

FW<br />

DB<br />

DB<br />

Output<br />

frequency<br />

Output<br />

frequency<br />

A055<br />

(Example 3-a)<br />

(Example 3-b)<br />

FW<br />

FW<br />

DB<br />

DB<br />

Output<br />

frequency<br />

Free running<br />

Output<br />

frequency<br />

Free running<br />

A053 A055 A053<br />

4 - 21