Chapter 4 Explanation of Functions<br />
4.2.19 DC braking (DB) setting<br />
The DC braking function allows you to apply DC braking to the<br />
motor according to the load on the motor.<br />
You can control DC braking in two ways: the external control<br />
through signal input to intelligent input terminals and the internal<br />
control to be performed automatically when the motor is started<br />
and stopped.<br />
Note that the motor cannot be stopped by DC braking if the load<br />
on the motor produces a large moment of inertia.<br />
Related code<br />
A051: DC braking enable<br />
A052: DC braking frequency setting<br />
A053: DC braking wait time<br />
A054: DC braking force during deceleration<br />
A055: DC braking time for deceleration<br />
A056: DC braking/edge or level detection for<br />
[DB] input<br />
A057: DC braking force for starting<br />
A058: DC braking time for starting<br />
A059: DC braking carrier frequency setting<br />
C001 to C008: Terminal [1] to [8] functions<br />
Item Function code Data or range of data Description<br />
00 Internal DC braking is disabled.<br />
01 Internal DC braking is enabled.<br />
DC braking enable A051<br />
Internal DC braking is enabled. (The braking<br />
02<br />
operates only with the set braking frequency.)<br />
DC braking<br />
frequency setting<br />
DC braking wait<br />
time<br />
DC braking force<br />
during deceleration/<br />
DC braking force for<br />
starting<br />
DC braking time for<br />
deceleration<br />
DC braking/edge or<br />
level detection for<br />
[DB] input<br />
DC braking time for<br />
starting<br />
A052<br />
A053<br />
A054/A057<br />
A055<br />
A056<br />
A058<br />
DC braking carrier<br />
A059<br />
frequency setting<br />
(NOTE) :applied for 75 to 150kW<br />
0.00 to 60.00 (Hz)<br />
0.0 to 5.0 (s)<br />
0. to 100. (%)<br />
<br />
With internal DC braking enabled, DC braking is<br />
started when the output frequency reaches the<br />
set braking frequency.<br />
The DC braking wait time specifies the delay in<br />
starting DC braking after the set braking time has<br />
elapsed or the DB terminal has been turned on.<br />
"0" specifies the smallest force (zero current);<br />
"100" specifies the largest force (rated current).<br />
0.0 to 60.0 (s)<br />
This setting is valid for the external DC braking in<br />
edge mode or for the internal DC braking.<br />
00 Edge mode (See examples 1-a to 6-a.)<br />
01 Level mode (See examples 1-b to 6-b.)<br />
0.0 to 60.0 (s)<br />
0.5 to 15 (kHz)<br />
<br />
This setting is valid for the internal DC braking.<br />
DC braking is started when the motor-start<br />
command is input.<br />
Unit: kHz<br />
(1) Carrier frequency for DC braking<br />
Use the DC braking carrier frequency setting (A059) to specify the carrier frequency for DC braking.<br />
But the raking power reduced is reduced when 5Hz (up to 55kW) or 3Hz (75-150kW) are set as shown<br />
below. For detailed decreasing ratio, "DC braking limiter" is to be referred.<br />
Maximum<br />
braking<br />
force (%)<br />
100<br />
90<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
(75)<br />
(46)<br />
(34)<br />
(22)<br />
(10)<br />
Maximum<br />
braking<br />
force (%)<br />
100<br />
90<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
(60)<br />
(40)<br />
(20)<br />
(10)<br />
0<br />
3 5 7 9 1 1 1<br />
DC braking carrier frequency<br />
(kHz)<br />
DC braking force limiter(0.4-55kW)<br />
0<br />
3<br />
4<br />
5<br />
DC braking carrier frequency<br />
(kHz)<br />
DC braking force limiter(75-150kW)<br />
6<br />
7<br />
8<br />
9<br />
1<br />
4 - 20