Chapter 4 Explanation of Functions<br />

(3) Free V/f characteristic setting<br />

The free V/f characteristic setting function allows you to set an arbitrary V/f characteristic by specifying the<br />

voltages and frequencies (b100 to b113) for the seven points on the V/f characteristic curve.<br />

The free V/f frequencies (1 to 7) set by this function must always be in the collating sequence of "1 ≤ 2 ≤ 3<br />

≤ 4 ≤ 5 ≤ 6 ≤ 7".<br />

Since all free V/f frequencies are set to 0 Hz as default (factory setting), specify their arbitrary values<br />

(begin setting with free-setting V/f frequency (7)). (The inverter cannot operate with the free V/f<br />

characteristic in the factory setting.)<br />

Enabling the free V/f characteristic setting function disables the torque boost selection (A041/A241), base<br />

frequency setting (A003/A203/A303), and maximum frequency setting (A004/A204/A304). (The inverter<br />

assumes the value of free-setting V/f frequency (7) as the maximum frequency.)<br />

Item Function code Data Description<br />

Free-setting V/f frequency (7) b112 0.to 400.(Hz)<br />

Free-setting V/f frequency (6) b110 0. to free-setting V/f frequency (7) (Hz)<br />

Free-setting V/f frequency (5) b108 0. to free-setting V/f frequency (6) (Hz)<br />

Free-setting V/f frequency (4) b106 0. to free-setting V/f frequency (5) (Hz)<br />

Free-setting V/f frequency (3) b104 0. to free-setting V/f frequency (4) (Hz)<br />

Free-setting V/f frequency (2) b102 0. to free-setting V/f frequency (3) (Hz)<br />

Free-setting V/f frequency (1) b100 0. to free-setting V/f frequency (2) (Hz)<br />

Free-setting V/f voltage (7)<br />

Free-setting V/f voltage (6)<br />

Free-setting V/f voltage (5)<br />

Free-setting V/f voltage (4)<br />

Free-setting V/f voltage (3)<br />

Free-setting V/f voltage (2)<br />

Free-setting V/f voltage (1)<br />

b113<br />

b111<br />

b109<br />

b107<br />

b105<br />

b103<br />

b101<br />

0.0 to 800.0(V)<br />

Setting of the output<br />

frequency at each<br />

breakpoint of the V/f<br />

characteristic curve<br />

Setting of the output<br />

voltage at each<br />

breakpoint of the V/f<br />

characteristic curve (*1)<br />

(Example)<br />

Output voltage (V)<br />

V7<br />

V6<br />

V5<br />

V4<br />

V1<br />

V2,V3<br />

0<br />

f1 f2 f3 f4 f5 f6 f7<br />

Output frequency (Hz)<br />

*1 Even if 800 V is set as a free-setting V/f voltage (1 to 7), the inverter output voltage cannot exceed the<br />

inverter input voltage or that specified by the AVR voltage select.<br />

Carefully note that selecting an inappropriate control system (V/f characteristic) may result in<br />

overcurrent during motor acceleration or deceleration or vibration of the motor or other machine driven<br />

by the inverter.<br />

Output voltage (V)<br />

V7<br />

Voltage that can be output by the<br />

inverter or that was specified by<br />

the AVR voltage select<br />

V6<br />

0 f6 f7<br />

4 - 17<br />

Output frequency (Hz)