Chapter 4 Explanation of Functions<br />

(2) Start/end frequency settings for the O2-L terminal<br />

Item Function code Range of data Description Remarks<br />

02 start frequency A111 -400. to 400.(Hz) Setting of the start frequency<br />

02 end frequency A112 -400. to 400.(Hz) Setting of the end frequency<br />

02 start-frequency<br />

rate<br />

02 end-frequency<br />

rate<br />

A113 -100. to 100.(%)<br />

A114 -100. to 100.(%)<br />

Setting of the rate of the start frequency<br />

to the external frequency command (-10<br />

to +10 V) (*1)<br />

Setting of the rate of the end frequency<br />

to the external frequency command (-10<br />

to +10 V) (*1)<br />

(Example 3)<br />

*1 The frequency rates correspond to the voltages<br />

(-10 to +10 V) of the external frequency command<br />

as follows:<br />

-10 to 0 V: -100% to 0%<br />

0 to +10 V: 0% to 100%<br />

For example, if the voltage of the signal to be input to<br />

the O2-L terminal is -5 to +5 V, specify 50% for "A114".<br />

(Example 3)<br />

Maximum frequency for<br />

forward operation<br />

(-10V)<br />

-100%<br />

A113<br />

A112<br />

A111<br />

A114<br />

100%<br />

(+10V)<br />

Analog input<br />

(O2)<br />

4.2.15 External analog input (O/OI/O2) filter setting<br />

The external analog input filter setting function allows you to set the<br />

input-voltage/input-current sampling time to be applied when frequency<br />

commands are input as external analog signals.<br />

You can use this filter function effectively for removing noise from the frequency-setting circuit signal.<br />

If the noise disables the stable operation of the inverter, increase the setting. Setting a larger value makes<br />

the inverter response slower. The filtering constant is "set value (1 to 30) x 2 ms."<br />

When the setting is "31" (factory setting), a hysteresis of ±0.1 Hz is added to the filtering constant (500<br />

ms).<br />

Item Function code Range of data Description<br />

External frequency filter<br />

time const.<br />

4.2.16 V/f gain setting<br />

A016 1. to 30. or 31.<br />

The V/f gain setting function allows you to change the inverter output<br />

voltage by specifying the rate of the output voltage to the voltage (100%)<br />

selected with the AVR voltage select function (A082).<br />

If the motor operation is cranky, try to increase the gain setting.<br />

Maximum frequency for<br />

reverse operation<br />

Related code<br />

A016: External frequency filter time<br />

const.<br />

Setting of 1. to 30.: "Set value x 2" ms filter<br />

Setting of 31.: 500 ms filter (fixed) with hysteresis<br />

of ±0.1 Hz<br />

Related code<br />

A045: V/f gain setting<br />

A082: AVR voltage select<br />

Item Function code Range of data Description<br />

V/f gain setting A045 20. to 100. (%) Setting of the rate of reducing the output voltage<br />

AVR voltage<br />

select<br />

(100%)<br />

A045<br />

Base<br />

frequency<br />

Maximum<br />

frequency<br />

4 - 15