Chapter 4 Explanation of Functions<br />
(Example 1) When<br />
the motor operation<br />
is not reversible<br />
(Example 1) When<br />
the motor operation<br />
is reversible<br />
FW<br />
FW<br />
AT<br />
Main frequency<br />
command via the OI<br />
or O terminal<br />
0<br />
fOI<br />
fO<br />
fO2<br />
AT<br />
Main frequency<br />
command via the OI<br />
or O terminal<br />
0<br />
fOI<br />
fO<br />
fO2<br />
Auxiliary<br />
frequency<br />
command via<br />
the O2 terminal<br />
0<br />
Auxiliary<br />
frequency<br />
command via<br />
the O2 terminal<br />
0<br />
fO + fO2<br />
fOI +fO2<br />
fO + fO2<br />
fOI +fO2<br />
Actual frequency<br />
command<br />
0<br />
Forward<br />
operation<br />
Actual frequency<br />
command<br />
0<br />
Forward<br />
operation<br />
Reverse<br />
operation<br />
4.2.12 Frequency operation function<br />
Related code<br />
A141: Operation-target frequency selection 1<br />
The frequency operation function allows you to use the result of an<br />
A142: Operation-target frequency selection 2<br />
arithmetic operation on two frequency commands as the actual A143: Operator selection<br />
frequency command or PID feedback data.<br />
A001: Frequency source setting<br />
A076: PV source setting<br />
To use the operation result as the actual frequency command,<br />
specify "10" for the frequency source setting (A001).<br />
To use the operation result as the PID feedback data, specify "10" for the PV source setting (A076).<br />
Item Function code Data Description<br />
00 Digital operator (A020/A220/A320)<br />
(01)<br />
Control on the digital operator<br />
(Valid only when the OPE-SR is connected)<br />
02 Input via the O terminal<br />
Operation-target frequency<br />
A141/A142 03 Input via the OI terminal<br />
selection 1 and 2<br />
04 Input via the RS485 terminal<br />
05 Input from option board 1<br />
06 Input from option board 2<br />
07 Input of pulse train<br />
00 Addition: (A141) + (A142)<br />
A143<br />
01 Subtraction: (A141) - (A142)<br />
Operator selection for<br />
frequency operation<br />
02 Multiplication: (A141) x (A142)<br />
Frequency source setting A001 10 Output of operation result<br />
PV source setting A076 10 Output of operation result<br />
Note 1: The [1] (up) and [2] (down) keys of the digital operator are ineffective when the frequency<br />
operation function is enabled. Also, the frequency displayed by the output frequency monitoring<br />
(d001), Scaled output frequency monitoring (d007), or output frequency setting (F001) cannot be<br />
changed with key operations.<br />
Note 2: The settings of "A141" and "A142" can be the same.<br />
4 - 13