Chapter 4 Explanation of Functions<br />

4.2.11 External analog input setting (O, OI, and O2)<br />

The inverter has the following three types of external analog input<br />

terminals:<br />

O-L terminal: 0 to 10 V<br />

OI-L terminal: 4 to 20 mA<br />

O2-L terminal: -10 to 10 V<br />

Related code<br />

A005: [AT] selection<br />

A006: [O2] selection<br />

C001 to C008: Terminal [1] to [8] functions<br />

The table below lists the settings of the external analog input terminals.<br />

Item<br />

[AT]<br />

selection<br />

[O2]<br />

selection<br />

Function<br />

code<br />

A005<br />

A006<br />

Data<br />

Description<br />

00<br />

Switching between the O and OI Turning on the AT terminal enables the OI-L terminal.<br />

terminals with the AT terminal<br />

Turning on the AT terminal enables the O-L terminal.<br />

01<br />

Switching between the O and O2 Turning on the AT terminal enables the O2-L terminal.<br />

terminals with the AT terminal<br />

Turning on the AT terminal enables the O-L terminal.<br />

(02)<br />

(Valid only when the OPE-SR is used)<br />

Switching between the O terminal and<br />

the control with the AT terminal<br />

Turning on the AT terminal enables the pot on<br />

OPE-SR terminal.<br />

Turning on the AT terminal enables the O-L terminal.<br />

(03)<br />

(Valid only when the OPE-SR is used)<br />

Switching between the OI terminal and<br />

the control with the AT terminal<br />

Turning on the AT terminal enables the pot on<br />

OPE-SR terminal.<br />

Turning on the AT terminal enables the OI-L terminal.<br />

(Valid only when the OPE-SR is used) Turning on the AT terminal enables the pot on<br />

(04) Switching between the O2 terminal<br />

OPE-SR terminal.<br />

and the control with the AT terminal Turning on the AT terminal enables the O2-L terminal.<br />

00 Using the O2 terminal independently<br />

01<br />

Using the O2 terminal for auxiliary frequency command (nonreversible) in addition to the O and<br />

OI terminals<br />

02<br />

Using the O2 terminal for auxiliary frequency command (reversible) in addition to the O and OI<br />

terminals<br />

03 Disabling the O2 terminal<br />

Note that whether frequency commands are input to the O2-L terminal and whether the motor operation is<br />

reversible depend on the combination of settings of functions "A005" and "A006" and whether function "16"<br />

(AT) is assigned to an intelligent input terminal as shown in the table below.<br />

When the motor operation is reversible, the inverter operates the motor in a reverse direction if the sum of<br />

the frequencies specified by the main frequency and auxiliary frequency commands is less than 0 (even<br />

when the forward operation [FW] terminal is on). Even when no wire is connected to the 02 terminal,<br />

reverse operation of the motor may occur and prolong the acceleration time if the output voltage fluctuates<br />

near 0 V.<br />

When the AT<br />

function is<br />

assigned to an<br />

intelligent input<br />

terminal<br />

When the AT<br />

function is not<br />

assigned to any<br />

intelligent input<br />

terminal<br />

A006<br />

A005<br />

AT<br />

terminal<br />

Main frequency command<br />

Whether to input an auxiliary<br />

frequency command<br />

(via the O2-L terminal)<br />

Reversible/<br />

nonreversible<br />

00,03<br />

00<br />

OFF O-L terminal No input<br />

ON OI-L terminal No input<br />

Nonreversible<br />

01<br />

OFF O-L terminal No input<br />

ON O2-L terminal No input Reversible<br />

00 OFF O-L terminal Input<br />

(Example 1) ON OI-L terminal Input<br />

Nonreversible<br />

01<br />

OFF O-L terminal Input<br />

01<br />

ON O2-L terminal No input Reversible<br />

00 OFF O-L terminal Input<br />

(Example 2) ON OI-L terminal Input<br />

02<br />

Reversible<br />

OFF O-L terminal Input<br />

01<br />

ON O2-L terminal No input<br />

00 - - O2-L terminal No input Reversible<br />

01 - -<br />

Addition of signals on O-L and<br />

OI-L terminals<br />

Input<br />

Nonreversible<br />

02 - -<br />

Addition of signals on O-L and<br />

OI-L terminals<br />

Input<br />

Reversible<br />

03 - -<br />

Addition of signals on O-L and<br />

OI-L terminals<br />

No input<br />

Nonreversible<br />

4 - 12