Chapter 4 Explanation of Functions<br />

4.2.6 Stop mode selection<br />

The stop mode selection function allows you to select one of<br />

two methods of stopping the motor when a stop command is<br />

input from the digital operator or via the control circuit terminal<br />

block. One is to decelerate the motor according to the specified<br />

deceleration time and then stop it; the other is to let the motor<br />

run freely until it stops.<br />

If a start command is input while the motor is in free-running status, the inverter will restart the motor<br />

according to the setting of the restart mode after FRS (b088). (See Section 4.2.47.)<br />

Item Function code Data Description<br />

Stop mode<br />

00 Normal stopping (stopping after deceleration)<br />

b091<br />

selection<br />

01 Free-running until stopping<br />

Restart mode after<br />

00 Starting with 0 Hz<br />

b088<br />

FRS<br />

01 Starting with matching frequency<br />

Restart frequency<br />

Starting with 0 Hz if the frequency-matching result is<br />

b007 0.00 to 400.0(Hz)<br />

threshold<br />

less than the set lower limit<br />

Retry wait time<br />

Time to wait until the restart of the motor after<br />

b003 0.3 to 100.(s)<br />

before motor restart<br />

free-running ends<br />

4.2.7 STOP key enable<br />

When the control circuit terminal block is selected as the device to input<br />

operation commands, the STOP key enable function allows you to enable<br />

or disable the motor-stopping and trip reset functions of the STOP key of<br />

the digital operator.<br />

Related code<br />

b091: Stop mode selection<br />

F003/F203/F303:<br />

Deceleration (1) time setting,<br />

1st/2nd/3rd motors<br />

b003: Retry wait time before motor restart<br />

b007: Restart frequency threshold<br />

b008: Restart mode after FRS<br />

Related code<br />

b087: STOP key enable<br />

This function is effective only when the digital operator (02) is not specified for the run command source<br />

setting (A002) (see Section 4.2.5).<br />

If the digital operator (02) is specified for "A002", the motor-stopping and trip reset functions of the STOP<br />

key are enabled regardless of this setting (STOP key enable).<br />

Function code Data Stop command with STOP key Trip reset command with STOP key<br />

00 Enabled Enabled<br />

b087<br />

01 Disabled Disabled<br />

02 Disabled Enabled<br />

4 - 9