Chapter 4 Explanation of Functions<br />

4.2 Function Mode<br />

4.2.1 Output frequency setting<br />

The output frequency setting function allows you to set the inverter<br />

output frequency.<br />

You can set the inverter output frequency with this function (F001)<br />

only when you have specified "02" for the frequency source setting<br />

(A001). For other methods of frequency setting, see Section 4.2.4,<br />

"frequency source setting (A001)."<br />

Related code<br />

F001: Output frequency setting<br />

A001: Frequency source setting<br />

A020/A220/A320:<br />

Multispeed frequency setting,<br />

1st/2nd/3rd motors<br />

C001 to C008:<br />

Terminal [1] to [8] functions<br />

(If the setting of function "A001" is other than "02", function "F001" operates as the frequency command<br />

monitoring function.)<br />

The frequency set with function "F001" is automatically set as the Multispeed frequency setting (A020). To<br />

set the second and third multispeed s, use the multispeed frequency setting, 2nd motor, function (A220)<br />

and multispeed frequency setting, 3rd motor, function (A320), or use function "F001" for the setting after<br />

turning on the SET and SET3 signals. For the setting using the SET and SET3 signals, assign the SET<br />

function (08) and SET3 function (17) to intelligent input terminals.<br />

If the set output frequency is used as the target data for the PID function, PID feedback data will be<br />

displayed in percent (%). ("100%" indicates the maximum frequency.)<br />

Item Function code Range of data Description<br />

Output frequency setting F001<br />

The frequency set with F001 is equal to the<br />

0.0, start frequency to setting of A020.<br />

Multispeed 0<br />

maximum frequency, The second control frequency set with F001<br />

A020/A220/<br />

1st/2nd/3rd motors is equal to the setting of A220.<br />

A320<br />

(Hz)<br />

The third control frequency set with F001 is<br />

equal to the setting of A320.<br />

4.2.2 Keypad Run key routing<br />

Related code<br />

When you enter operation commands via the digital operator, the Keypad F004: Keypad Run key routing<br />

Run key routing function allows you to select the direction of motor<br />

operation.<br />

This function is ineffective when you use the control terminal block or remote operator to input operation<br />

commands.<br />

Item Function code Data Description<br />

00 Forward operation<br />

Keypad Run key routing F004<br />

01 Reverse operation<br />

4.2.3 Rotational direction restriction<br />

Related code<br />

The rotational direction restriction function allows you to restrict the<br />

b035: Rotational direction restriction<br />

direction of motor operation.<br />

This function is effective regardless of the specification of operation command input device (e.g., control<br />

circuit block or digital operator).<br />

If an operation command to drive the motor in a restricted direction is input, the inverter (digital operator)<br />

will display .<br />

Item Function code Data Description<br />

00 Both forward and reverse operations are enabled.<br />

Rotational direction<br />

b035<br />

01 Only forward operation is enabled.<br />

restriction<br />

02 Only reverse operation is enabled.<br />

4 - 7