Chapter 4 Explanation of Functions<br />
4.1.8 Actual-frequency monitoring<br />
The actual-frequency monitoring function is effective only when a motor<br />
equipped with an encoder is connected to the inverter and the feedback<br />
option board (SJ-FB) is mounted in the inverter. When the<br />
actual-frequency monitoring function (d008) is selected, the inverter<br />
displays the actual operating frequency of the motor (regardless of the<br />
motor control method (A044 or A244)).<br />
(Display)<br />
Forward operation:<br />
0.00 to 99.99 in steps of 0.01 Hz<br />
100.0 to 400.0 in steps of 0.1 Hz<br />
Reverse operation:<br />
- 0.0 to -99.9 in steps of 0.1 Hz<br />
- 100 to -400 in steps of 1 Hz<br />
Note:<br />
To use this monitoring function, set the encoder pulse-per-revolution (PPR) setting (P011) and the<br />
number of motor poles (H004 or H204) correctly.<br />
4.1.9 Torque command monitoring<br />
Related code<br />
d009: Torque command monitoring<br />
The torque command monitoring function is effective when you have P033: Torque command input selection<br />
selected control by torque for the vector control with sensor. When the P034: Torque command setting<br />
torque command monitoring function (d009) is selected, the inverter<br />
A044: V/f characteristic curve selectcion<br />
C001 to C008: Terminal [1] to [8]<br />
displays the value of the currently input torque command.<br />
The % monitor lamp lights up while the inverter is displaying the torque command value.<br />
Assign 52 (ATR) on intelligent input terminal and turn on to activate torque control.<br />
(Display)<br />
0. to 200. in steps of 1 %<br />
4.1.10 Torque bias monitoring<br />
The torque bias monitoring function is effective when you have selected<br />
the vector control with sensor. When the torque bias monitoring function<br />
(d010) is selected, the inverter displays the value of the currently set<br />
value of torque bias.<br />
The % monitor lamp lights up while the inverter is displaying the torque bias value.<br />
(Display)<br />
-150. to +150. in steps of 1 %<br />
Related code<br />
d008: Actual-frequency monitoring<br />
P011: Encoder pulse-per-revolution<br />
(PPR) setting<br />
H004: Motor poles setting, 1st motor<br />
H204: Motor poles setting, 2nd motor<br />
Related code<br />
d010: Torque bias monitoring<br />
A044: V/f characteristic curve selectcion<br />
P036: Torque bias mode<br />
P037: Torque bias value<br />
P038: Torque bias polarity<br />
4.1.11 Torque monitoring<br />
Related code<br />
When the torque monitoring function (d012) is selected, the inverter d012: Torque monitoring<br />
displays the estimated value of the torque output from the inverter.<br />
A044: V/f characteristic curve selectcion<br />
The % monitor lamp lights up while the inverter is displaying the estimated output torque.<br />
(Display)<br />
-300. to +300. in steps of 1 %<br />
Note: This monitoring function is effective only when you have selected the sensorless vector control,<br />
0Hz-range sensorless vector control, or vector control with sensor as the control mode.<br />
Displayed value is not accurate when the other control method is selected.<br />
4.1.12 Output voltage monitoring<br />
Related code<br />
When the output voltage monitoring function (d013) is selected, the d013: Output voltage monitoring<br />
inverter displays the voltage output from the inverter.<br />
The V monitor lamp lights up while the inverter is displaying the output voltage.<br />
(Display)<br />
0.0 to 600.0 in steps of 0.1 V<br />
(remark) Displayed value may not be accurate when the output voltage is differ from input voltage.<br />
4.1.13 Power monitoring<br />
Related code<br />
When the power monitoring function (d014) is selected, the inverter d014: Power monitoring<br />
displays the electric power (momentary value) input to the inverter.<br />
The kW monitor lamps (V and A lamps) light up while the inverter is displaying the input power.<br />
(Display)<br />
0.0 to 999.9 in steps of 0.1 kW<br />
4 - 3