29.01.2015 Views

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 4 Explanation of Functions<br />

4.1 Monitor Mode<br />

4.1.1 Output frequency monitoring<br />

Related code<br />

When the output frequency monitoring function (d001) is selected, the d001: Output frequency monitoring<br />

inverter displays the output frequency. The inverter displays "0.00" when<br />

the frequency output is stopped.<br />

The Hz monitor lamp lights up while the inverter is displaying the output frequency.<br />

(Display)<br />

0.00 to 99.99 in steps of 0.01 Hz<br />

100.0 to 400.0 in steps of 0.1 Hz<br />

Note: When you have selected the digital operator as the device to input frequency-setting commands<br />

(A001=02), you can change the output frequency setting by using the △and/or ▽ key (only while<br />

the inverter is operating the motor).<br />

- The change in output frequency made in this mode can be reflected in the frequency setting<br />

(function "F001"). Press the STR key to write the new frequency over the currently selected<br />

frequency setting.<br />

- You cannot change the output frequency while the PID function is enabled or the inverter is not<br />

operating the motor.<br />

4.1.2 Output current monitoring<br />

Related code<br />

When the output current monitoring function (d002) is selected, the<br />

d002: Output current monitoring<br />

inverter displays the output current. The inverter displays "0.0" when the<br />

current output is stopped.<br />

The A monitor lamp lights up while the inverter is displaying the output current.<br />

(Display)<br />

0.0 to 999.9 in steps of 0.1 A<br />

4.1.3 Rotation direction monitoring<br />

Related code<br />

When the rotation direction monitoring function (d003) is selected, the d003: Rotation direction monitoring<br />

inverter displays the motor operation direction.<br />

The RUN lamp lights up while the inverter is operating the motor (in forward or reverse direction).<br />

(Display)<br />

F: Forward operation<br />

o: Motor stopped<br />

r: Reverse operation<br />

4.1.4 Process variable (PV), PID feedback monitoring<br />

When "01" (enabling PID operation) or "02" (enabling inverted-data<br />

output) has been specified for function "A071" (PID Function Enable) and<br />

the process variable (PV), PID feedback monitoring function (d004) is<br />

selected, the inverter displays the PID feedback data.<br />

Related code<br />

d004: Process variable (PV), PID<br />

feedback monitoring<br />

A071: PID Function Enable<br />

A075: PV scale conversion<br />

You can also convert the PID feedback to gain data by setting a PV scale conversion (with function<br />

"A075").<br />

Value displayed by function "d004" = "feedback quantity" (%) x " PV scale conversion (A075)"<br />

The PV scale conversion can be set (by function "A075") within the range 0.01 to 99.99 in steps of 0.01.<br />

(Display)<br />

0.00 to 99.99 in steps of 0.01<br />

100.0 to 999.9 in steps of 0.1<br />

1000. to 9999. in steps of 1<br />

⎡100 to ⎡999 in units of 10<br />

4 - 1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!