Chapter 3 Operation<br />

- Use the 1 and/or 2 key to change the displayed value to "00" for forward operation or "01" for<br />

reverse operation, and then press the STR key once to determine the operation direction.<br />

(The display reverts to [F004].)<br />

7) Set the monitor mode.<br />

- To monitor the output frequency, display the function code "d001", and then press the FUNC key once.<br />

(The monitor shows the output frequency.)<br />

FUNC<br />

To monitor the operation direction, display the function code "d003", and then press the key<br />

once.<br />

(The monitor shows for forward operation, for reverse operation, or for stopping.)<br />

8) Press the RUN key to start the motor.<br />

(The RUN lamp [green LED] goes on.)<br />

STOP/<br />

9) Press the RESET key to decelerate or stop the motor.<br />

(When the motor stops, the RUN lamp [green LED] goes off.)<br />

- During the test run, confirm that the inverter does not trip while accelerating or decelerating the motor<br />

and that the motor speed and frequencies are correct.<br />

- If a trip due to overcurrent or overvoltage has occurred during the test run, increase the acceleration<br />

and deceleration time.<br />

- Make sure that there is enough margin to trip level by monitoring the output current (d002) and DC<br />

voltage (d102).<br />