29.01.2015 Views

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 2 Installation and Wiring<br />

(6) Installation method and position<br />

Install the inverter vertically and securely with screws or bolts on a surface that is free from vibrations<br />

and that can bear the inverter weight.<br />

If the inverter is not installed vertically, its cooling performance may be degraded and tripping or<br />

inverter damage may result.<br />

(7) Mounting in an enclosure<br />

When mounting multiple inverters in an enclosure with a ventilation fan, carefully design the layout of<br />

the ventilation fan, air intake port, and inverters.<br />

An inappropriate layout will reduce the inverter-cooling effect and raise the ambient temperature. Plan<br />

the layout so that the inverter ambient temperature will remain within the allowable range.<br />

Ventilation fan<br />

Ventilation fan<br />

Inverter<br />

Inverter<br />

(Acceptable)<br />

(Unacceptable)<br />

Position of ventilation fan<br />

(8) Reduction of enclosure size<br />

If you mount the inverter inside an enclosure such that the heat sink of the inverter is positioned<br />

outside the enclosure, the amount of heat produced inside the enclosure can be reduced and likewise<br />

the size of the enclosure.<br />

Mounting the inverter in an enclosure with the heat sink positioned outside requires an optional<br />

dedicated special metal fitting.<br />

To mount the inverter in an enclosure with the heat sink positioned outside, cut out the enclosure panel<br />

according to the specified cutting dimensions.<br />

The cooling section (including the heat sink) positioned outside the enclosure has a cooling fan.<br />

Therefore, do not place the enclosure in any environment where it is exposed to waterdrops, oil mist,<br />

or dust.<br />

(9) Approximate loss by inverter capacity<br />

Inverter capacity (kW)<br />

0.4 0.75 1.5 2.2<br />

3.7<br />

(4.0)<br />

5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110<br />

132<br />

(150)<br />

Loss with 70% load (W) 64 76 102 127 179 242 312 435 575 698 820 1100 1345 1625 1975 2675 3375 3900 4670<br />

Loss with 100% load (W) 70 88 125 160 235 325 425 600 800 975 1150 1550 1900 2300 2800 3800 4800 5550 6650<br />

Efficiency at rated output (%) 85.1 89.5 92.3 93.2 94.0 94.4 94.6 94.8 94.9 95.0 95.0 95.0 95.1 95.1 95.1 95.2 95.2 95.2 95.2<br />