Chapter 6 Maintenance and Inspection<br />

Increase the voltage to 90% and keep for 1 hour.<br />

Then apply rated voltage for 5 hours.<br />

*5 In case fan is locked by dust or particle, it takes 5 to 10 seconds to restart even after the dust is removed.<br />

6.3 Ground Resistance Test with a Megger<br />

When testing an external circuit with a megger, disconnect all the external circuit cables from the inverter<br />

to prevent it from being exposed to the test voltage.<br />

Use a tester (in high-resistance range mode) for a conduction test on the control circuit. Do not use a<br />

megger or buzzer for that purpose.<br />

Apply the ground resistance test using a megger only to the main circuit of the inverter. Do not carry out<br />

the test using a megger for its control circuit.<br />

Use a 500 VDC megger for the ground resistance test.<br />

Before the main circuit test with a megger, remove the jumper for switching the inverter's internal filter<br />

function, and then connect terminals R, S, T, U, V, W, P, PD, N, RB, R0, and T0 by wires as shown in the<br />

figure below. Subsequently, carry out the test.<br />

After the test using the megger, remove the wires from terminals R, S, T, U, V, W, P, PD, N, RB, R0, and T0,<br />

and connect the jumper for switching the inverter's internal filter function at the original position.<br />

Note that only inverter models with a capacity of less than 22 kW have the RB terminal.<br />

Power supply<br />

Do not connect<br />

power supply cables<br />

to the inverter.<br />

500 VDC megger<br />

R<br />

S<br />

T<br />

R0<br />

T0<br />

P P N R<br />

Ground<br />

terminal<br />

U<br />

V<br />

Ground W<br />

terminal<br />

Motor<br />

IM<br />

Do not connect the<br />

inverter cables to the<br />

motor.<br />

Be sure to remove the jumper for<br />

switching the internal filter function.<br />

6.4 Withstand Voltage Test<br />

Do not carry out a withstand voltage test for the inverter. The test may damage its internal parts or cause<br />

them to deteriorate.<br />

6 - 3