Chapter 5 Error Codes<br />

3) Error indications by protective functions with the DeviceNet option board (SJ-DN) mounted<br />

Name<br />

DeviceNet<br />

communicatio<br />

n error<br />

Duplicate<br />

MAC ID<br />

External trip<br />

Inverter<br />

communicatio<br />

n error<br />

Description<br />

If the disconnection due to the Bus-Off<br />

signal or timeout occurs during the<br />

operation using DeviceNet commands,<br />

the inverter will shut off its output and<br />

display the error code shown on the right.<br />

(The inverter will trip according to the<br />

settings of "p45" and "P048".)<br />

If two or more devices having the same<br />

MAC ID are detected in the same<br />

network, the inverter will display the error<br />

code shown on the right.<br />

If the Force Fault/Trip bit of Attribute 17 in<br />

the Instance 1 of the Control Supervisory<br />

object is set to "1", the inverter will shut<br />

off its output and display the error code<br />

shown on the right.<br />

If timeout occurs during the<br />

communication between the inverter and<br />

DeviceNet option board, the inverter will<br />

shut off its output and display the error<br />

code shown on the right.<br />

Display on<br />

digital operator<br />

Display on<br />

remote operator<br />

OP1-0<br />

OP2-0<br />

OP1-1<br />

OP2-1<br />

OP1-2<br />

OP2-2<br />

OP1-9<br />

OP2-9<br />

Troubleshooting and corrective action<br />

Check whether the communication speed<br />

setting is correct.<br />

Check whether the wiring distance is<br />

appropriate.<br />

Check the connections.<br />

Check whether duplicate MAC IDs are<br />

used.<br />

Check whether the Attribute 17 in the<br />

Instance 1 of Class 29 is "1". (If so, clear<br />

the bit to "0".)<br />

Check whether the option board has been<br />

disconnected from the inverter.<br />

Reference<br />

page<br />

Refer to the<br />

instruction<br />

manual for<br />

the SJ-DN.<br />

Note: If the option board does not operate normally, confirm the DIP switch settings on the option board.<br />

Functions of the DIP switches on the DeviceNet option board (SJ-DN)<br />

Setting of DeviceNet baud rate (DIP switches No. 1 and No. 2)<br />

Baud rate 125 kbps 250 kbps 500 kbps<br />

DR<br />

ON<br />

DR<br />

ON<br />

DR<br />

ON<br />

DIP switch setting<br />

↓ ↓<br />

DR1 DRO<br />

OFF<br />

↓ ↑<br />

DR1 DRO<br />

OFF<br />

↑ ↓<br />

DR1 DRO<br />

OFF<br />

Setting of MAC ID (DIP switches No. 3 to No. 8)<br />

MAC ID<br />

Dip switch setting<br />

The left-most switch indicates the highest-order bit of MAC ID. Therefore, the<br />

example of switch settings shown on the left indicates the following MAC ID:<br />

= 29 (hexadecimal) = 41 (decimal)<br />

Note: For details, refer to the instruction manual for the option board.<br />

5 - 7