Chapter 5 Error Codes<br />
Name<br />
Option 2<br />
error<br />
Description<br />
The inverter detects errors in the option<br />
board mounted in the optional slot 2.<br />
For details, refer to the instruction<br />
manual for the mounted option board.<br />
If the input voltage falls, the inverter will<br />
shut off its output, display the code<br />
shown on the right, and wait for the<br />
recovery of the input voltage.<br />
Waiting in The inverter will display the same error<br />
undervoltage code also during an instantaneous<br />
status power failure.<br />
(remark) Inverter trips with under<br />
voltage when this status continues for<br />
40 seconds.<br />
Communication<br />
error<br />
Waiting for<br />
retry<br />
Power-off<br />
Restricted<br />
operation<br />
command<br />
Empty trip<br />
history<br />
If a problem occurs in the<br />
communication between the digital<br />
operator and inverter, the inverter will<br />
display the code shown on the right.<br />
When the retry after instantaneous<br />
power failure or tripping has been<br />
enabled, the inverter displays the code<br />
shown on the right while awaiting retry<br />
after an instantaneous power failure or<br />
tripping.<br />
The inverter displays the code shown<br />
on the right when the inverter power is<br />
turned off.<br />
When an operation direction has been<br />
restricted by the setting of "b035", the<br />
inverter will display the error code<br />
shown on the right if the operation<br />
command specifying the restricted<br />
operation direction is input.<br />
If the inverter has not tripped before,the<br />
inverter displays .<br />
Display on<br />
digital operator<br />
to<br />
Display on remote<br />
operator<br />
OP2-0<br />
OP2-9<br />
UV.WAIT<br />
R-ERROR COMM<br />
R-ERROR COMM<br />
RESTART<br />
ADJUST<br />
POWER OFF<br />
RUN.CMD DISABLE<br />
Ex. Err2<br />
Err2 <br />
Reference<br />
Troubleshooting and corrective action<br />
page<br />
Check whether the option board is<br />
Refer to the<br />
mounted correctly.<br />
instruction<br />
(Check the board mounting.)<br />
manual for<br />
Check whether the option board is used<br />
the SJ-FB,<br />
correctly.<br />
SJ-DG, or<br />
(Check the instruction manual for the<br />
SJ-DN.<br />
option board.)<br />
Check whether the power supply voltage<br />
has fallen.<br />
(Recover the power supply.)<br />
Check the MCB and magnetic contactors<br />
for poor contacts.<br />
(Replace the MCB and magnetic -<br />
contactors.)<br />
Check whether the voltage across the P<br />
and N terminals is normal.<br />
(Check the voltage across the P and N<br />
terminals.)<br />
Check whether the relay plug is fitted<br />
correctly.<br />
(Check the relay plug for connection.)<br />
-<br />
Check whether the digital operator is<br />
connected correctly.<br />
(Check the digital operator for connection.)<br />
-<br />
-<br />
-<br />