Chapter 4 Explanation of Functions<br />
Register<br />
Register<br />
Function name Function code R/W Monitoring and setting items Data resolution<br />
No.<br />
No.<br />
1470h (Reserved) R/W -<br />
1471h AM bias adjustment C109 R/W 0 to 100 1 [%]<br />
1472h AMI bias adjustment C110 R/W 0 to 100 1 [%]<br />
1473h Overload setting (2) C111 R/W 0 to 2000 0.1 [%]<br />
1474h to<br />
147Ch<br />
(Reserved) - - Inaccessible -<br />
147Dh [O] input zero calibration C121 R/W 0 to 65530 1<br />
147Eh [OI] input zero calibration C122 R/W 0 to 65530 1<br />
147Fh [O2] input zero calibration C123 R/W 0 to 65530 1<br />
1480h to<br />
1485h<br />
(Reserved) - - Inaccessible -<br />
1486h Output 11 on-delay time C130 R/W 0 to 1000 0.1 [sec.]<br />
1487h Output 11 off-delay time C131 R/W 0 to 1000 0.1 [sec.]<br />
1488h Output 12 on-delay time C132 R/W 0 to 1000 0.1 [sec.]<br />
1489h Output 12 off-delay time C133 R/W 0 to 1000 0.1 [sec.]<br />
148Ah Output 13 on-delay time C134 R/W 0 to 1000 0.1 [sec.]<br />
148Bh Output 13 off-delay time C135 R/W 0 to 1000 0.1 [sec.]<br />
148Ch Output 14 on-delay time C136 R/W 0 to 1000 0.1 [sec.]<br />
148Dh Output 14 off-delay time C137 R/W 0 to 1000 0.1 [sec.]<br />
148Eh Output 15 on-delay time C138 R/W 0 to 1000 0.1 [sec.]<br />
148Fh Output 15 off-delay time C139 R/W 0 to 1000 0.1 [sec.]<br />
1490h Output RY on-delay time C140 R/W 0 to 1000 0.1 [sec.]<br />
1491h Output RY off-delay time C141 R/W 0 to 1000 0.1 [sec.]<br />
1492h Logical output signal 1 selection 1 C142 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
1493h Logical output signal 1 selection 2 C143 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
1494h Logical output signal 1 operator selection C144 R/W 0 (AND), 1 (OR), 2 (XOR) -<br />
1495h Logical output signal 2 selection 1 C145 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
1496h Logical output signal 2 selection 2 C146 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
1497h Logical output signal 2 operator selection C147 R/W 0 (AND), 1 (OR), 2 (XOR) -<br />
1498h Logical output signal 3 selection 1 C148 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
1499h Logical output signal 3 selection 2 C149 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
149Ah Logical output signal 3 operator selection C150 R/W 0 (AND), 1 (OR), 2 (XOR) -<br />
149Bh Logical output signal 4 selection 1 C151 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
149Ch Logical output signal 4 selection 2 C152 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
149Dh Logical output signal 4 operator selection C153 R/W 0 (AND), 1 (OR), 2 (XOR) -<br />
149Eh Logical output signal 5 selection 1 C154 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
149Fh Logical output signal 5 selection 2 C155 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
14A0h Logical output signal 5 operator selection C156 R/W 0 (AND), 1 (OR), 2 (XOR) -<br />
14A1h Logical output signal 6 selection 1 C157 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
14A2h Logical output signal 6 selection 2 C158 R/W<br />
Same as the settings of C021 to C026 (except<br />
those of LOG1 to LOG6)<br />
-<br />
14A3h Logical output signal 6 operator selection C159 R/W 0 (AND), 1 (OR), 2 (XOR) -<br />
14A4h Response time of intelligent input terminal 1 C160 R/W 0 to 200<br />
14A5h Response time of intelligent input terminal 2 C161 R/W 0 to 200<br />
14A6h Response time of intelligent input terminal 3 C162 R/W 0 to 200<br />
14A7h Response time of intelligent input terminal 4 C163 R/W 0 to 200<br />
14A8h Response time of intelligent input terminal 5 C164 R/W 0 to 200<br />
14A9h Response time of intelligent input terminal 6 C165 R/W 0 to 200<br />
14AAh Response time of intelligent input terminal 7 C166 R/W 0 to 200<br />
14ABh Response time of intelligent input terminal 8 C167 R/W 0 to 200<br />
Response time of intelligent input terminal<br />
14ACh<br />
FW<br />
C168 R/W 0 to 200<br />
Multistage speed/position determination<br />
14ADh<br />
C169 R/W 0 to 200<br />
time<br />
14A4h to<br />
(Reserved) - - Inaccessible -<br />
1500h<br />
4 - 156