Chapter 4 Explanation of Functions<br />

4.4.2 Communication in Modbus-RTU mode<br />

(1) Communication protocol<br />

The communication between the inverter (slave) and external control system (master) is based on the<br />

following protocol:<br />

(1) (1)<br />

External control system<br />

Inverter<br />

(2)<br />

Waiting time (silent interval +<br />

communication wait time [C078])<br />

Time<br />

(3) Communication trip limit time (C077)<br />

(If reception timeout occurs, the inverter will<br />

operate according to the setting of the<br />

operation selection after communication<br />

error [C076].)<br />

(1): Query frame that is sent from the external control system to the inverter<br />

(2): Response frame that is sent from the inverter to the external control system<br />

(3): Communication trip limit time (C077)<br />

If the inverter cannot complete the reception of a query from the master system (external control<br />

system) within the communication trip limit time, after having sent a response to the preceding query,<br />

the inverter enters the status in which to receive the query from the beginning. Subsequently, the<br />

inverter returns no response to the master system.<br />

After reception timeout occurs, the inverter operates according to the setting of the selection of<br />

operation after communication error (C076). For details, see the table below. Monitoring of reception<br />

timeout begins when the first communication is performed after the inverter power has been turned on<br />

or the inverter has been reset. Reception timeout is monitored only when the inverter communicates<br />

with the master system.<br />

Item Function code Range of data Description<br />

00: Tripping<br />

The inverter trips (E41) after reception<br />

timeout.<br />

The inverter decelerates and stops the<br />

01: Tripping after<br />

motor, and then trips (E41) after reception<br />

stopping the motor<br />

timeout.<br />

Selection of operation<br />

after communication error<br />

Communication trip limit<br />

time setting<br />

C076<br />

02: Ignoring the errors<br />

03: Stopping the<br />

motor after<br />

free-running (FRS)<br />

04: Decelerating and<br />

stopping the motor<br />

Communication wait time C078 0. to 1000. (ms)<br />

The inverter ignores the error without tripping<br />

and alarm output.<br />

The inverter stops the motor after<br />

free-running without tripping and alarm<br />

output after reception timeout.<br />

The inverter decelerates and stops the motor<br />

without tripping and alarm output after<br />

reception timeout.<br />

C077 0.00 to 99.99 (s) Limit time to determine the reception timeout<br />

Time to wait until the inverter starts sending a<br />

response after reception of a query<br />

(excluding the silent interval)<br />

The inverter sends a response (frame (2)) always after receiving a query (frame (1)). The inverter does not<br />

actively output any frame to the external control system.<br />

4 - 130