Chapter 4 Explanation of Functions<br />

(viii) 07 command: This command writes data to a specified setting item in the inverter.<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command Parameter Data BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32, or FF (broadcast to all stations)<br />

Command Command to be transmitted 2 bytes 07<br />

Parameter Data parameter number 4 bytes See Note 14.<br />

Data<br />

Parameter data (decimal ASCII<br />

code)<br />

8 bytes See Note 13.<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

Note 14: Possible range of parameters is as follows.<br />

F002-, A001-, b001-, C001-, H001-, P001- (F001 is written with 01 command.)<br />

- Response frame<br />

Positive response: See Item (2)-(i) of this section.<br />

Negative response: See Item (2)-(ii) of this section.<br />

(ix) 08 command: This command initializes specified settings in the inverter.<br />

The setting items to be initialized follow the setting of the initialization mode (b084). When "b084" is "00",<br />

the trip history data is cleared.<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32, or FF (broadcast to all stations)<br />

Command Command to be transmitted 2 bytes 08<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

- Response frame<br />

Positive response: See Item (2)-(i) of this section.<br />

Negative response: See Item (2)-(ii) of this section.<br />

4 - 125